YZ Systems Milton Roy • 201 Ivyland Road • Ivyland, Pennsylvania • USA • 18974 • P: 281.362.6500 • www.yzsystems.com
Page 34
NJEX EUR ver. 08-2021
Section 6: Programming for Proportional-to-Time Operation
Or
pmp bat vmtr sig tnk
Odorant Output
0.010 lbs/pulse
Figure 64
Figure 65
pmp bat vmtr sig tnk
Odorant Output
0.010 kg/pulse
pmp bat vmtr sig tnk
Odorant Tank
10=Low (%) 90=High
Setting Operator Input Parameters,
Continued
When a new value has been chosen, press the
Enter
key to store the new value into memory. The entered
value will stop flashing when it has been loaded into
memory. Press the
Down Arrow
key to advance to the
next parameter.
The Odorant Output Setting
This controls the scaling of the odorant output relay in
lbs/pulse. This indicates how much odorant has been
injected with each pulse of the output relay located
TB1
, terminals
#19
and
#20
,
Document on page 117 in Appendix D: Documents
To set the odorant output
,
figure 64
, press and
release the
Select
key. The value entry will begin to
flash when selected. Use the
Up Arrow
key to in-
crease the value and the
Down Arrow
key to decrease
the value. When a new value has been chosen, press
the Enter key to store the new value into memory.
The entered value will stop flashing when it has been
loaded into memory. Press the
Down Arrow
key to
advance to the next parameter.
Odorant Tank
Optional Setup Note:
This parameter functions only if
a complete YZ Skid Mounted Tank System is supplied.
1.
Disabled:
no level monitoring,
0% = disabled,
both Low & High settings must be disabled
.
2.
Enabled:
0-100% level monitoring with two alarms
that may be triggered from this level reading, a
High Tank Level Tank Alarm, and a Low Tank Level
Tank Alarm.
To set the alarm level points
,
figure 65
, press and re-
lease the
Select
key. The Low Level value will begin to
flash when chosen. Use the
Up Arrow
key to increase
the value and the
Down Arrow
key to decrease the
value. This alarm should typically be set between 5%
and 25%. When a new value has been chosen, press
the
Enter
key to store the new Low Level Alarm setting
into memory. The entered value will stop flashing when
Summary of Contents for NJEX 6300G
Page 1: ...NJEX 6300G 7300G N A T U R A L G A S O D O R I Z A T I O N S Y S T E M...
Page 2: ......
Page 3: ...NJEX 6300G 7300G Instruction Operating Manual Version 08 2021...
Page 4: ......
Page 10: ......