YZ Systems Milton Roy • 201 Ivyland Road • Ivyland, Pennsylvania • USA • 18974 • P: 281.362.6500 • www.yzsystems.com
Page 9
NJEX 7300G ver.08-2018
Section 2: System Installation
Figure 9
Figure 10
Optional Heater
A.C. Connection
CAUTION:
Excessive tubing lengths should be avoided. Installa-
tion of the NJEX Odorization system should be as close
to the point of injection and Odorant Storage Tank as
possible. Maximum tubing length should not exceed 15’
(4.5 meters) with the tubing size maintained as indicated
in this manual. If longer tubing lengths are required
consult YZ Systems Technical Service Department at;
800.653.9435 or 281.362.6500.
3. Connect the odorant supply source to the odorant
inlet mainfold with the recommended 1/4” stainless
steel tubing,
figure 9
. A tank isolation valve should
be incorporated between the storage tank and this
connection,
figure 9.
4. Connect the regulated actuation gas source, of 75
psi (5.17 Bar) supplied by the NJEX system owner,
to the NJEX gas filter inlet fitting using a dielectric
union,
figure 9
.
• For Pipeline pressures less than 200 psig a single
cut regulator (Fisher 67 YZ P/N A3-0042 or
similar) adjustable to provide 75 psig to the inlet
gas filter on the NJEX enclosure should be ac-
ceptable.
• P/L pressure above 200 psig need a dual cut regu-
lation process:
1. Install the primary regulator on the pipeline
*Fisher 1301 YZ P/N A3-0274 or similar),
and adjust it to provide 150 psi to the sec-
ondary regulator.
2. Install the secondary regulator at the inlet
gas filter on the back of the NJEX enclosure
(Fisher 67 YZ P/N A3-0042 or similar), and
adjust it to provide 75 psig to the NJEX Sys-
tem should be acceptable.
3. 3/8” Stainless Steel tubing should be used
between the two regulators.
• Dual Pump enclosures, may require larger tubing
between the regulators, and the secondary regula-
tor may need to have a larger orifice (Fisher 64 or
similar), if both pumps run simultaneously.
Note:
In applications where the actuation gas supply
has a high water content and/or a low hydrocarbon dew
point, additional actuation gas filtration or heating of the
7300G system may be necessary. Bottled nitrogen can
also be used during cold operating conditions to avoid
condensation in the actuation gas supply line. Also,
an actuation gas source pressure of 75 psi (5.17 Bar)
should be adequate in most installations.
5. Connect the pipeline port of the odorant discharge
manifold to the pipeline connection using a dielectric
union and check valve,
figure 9.
6. If a heater option was specified with this odorizer,
120 / 240 VAC electricity
, should be connected to the
electrical inlet located on the lower side of the
enclosure using 1/2” conduit and appropriate pack
off. Power requirements for the heater are
1.67A for the 120VAC heater, and .833A for the
240VAC heater. Each heater is a thermostati cally
controlled 200Watt unit, figure 10. Dual unit enclo
sures may have dual heater elements. Values
provided are per heater element.
Odorant Discharge
Manifold Pipeline Port
Odorant Inlet
Connection
75 psi (5.17 Bar)
Regulated Actuation
Gas
Summary of Contents for NJEX 7300G
Page 1: ...NJEX 7300G N A T U R A L G A S O D O R I Z A T I O N S Y S T E M ...
Page 2: ......
Page 3: ...The NJEX 7300G Instruction Operating Manual Version 08 2018 ...
Page 4: ......
Page 10: ......