Page 30
NJEX 7300G ver.08-2018
Section 5: Programming for Proportional-to-Flow Operation
Setting Operator Input Parameters,
Continued
Alarm to Relay Delay
Is a programmable time that can be entered to allow
for a period of time to occur between the initial issu-
ance of an alarm and the actual remote reporting of
the alarm via the alarm relay output.
1. 0 = No Relay Contact Delay
2. 1 - 240 = Number of Minutes Delay
3. > 240 = Disabled, No Alarm Relay Contact will oc-
cur
To set the alarm delay time
,
figure 53,
press and
release the
Select
key. The Alarm to Delay value
will begin to flash when chosen. Use the
Up Arrow
key to increase the value and the
Down Arrow
key
to decrease the value. When a new value has been
chosen, press the
Enter
key to store the value.
Alarm to Call Out Delay
Is a programmable time that can be entered to allow
for a period of time to occur between the initial issu-
ance of an alarm and the actual automatic call out
function via a modem or Modbus communication port.
1. 0 = No Alarm Call Out Delay
2. 1 - 240 = Number of Minutes Delay
3. > 240 = Disabled, No Alarm Call Out will occur
To set the alarm to call out delay time
,
figure 54,
press and release the
Select
key. The Alarm to Call-
out Delay value will begin to flash when chosen. Use
the
Up Arrow
key to increase the value and the
Down
Arrow
key to decrease the value. When a new value
has been chosen, press the
Enter
key to store the
value.
MODBUS Address
In Modbus Protocol, each piece of equipment that will
be polled for information must be assigned a Slave I.D.
address, to allow the SCADA or other Host device to
properly address the device to be polled for information.
This parameter is to program the odorizer’s Modbus ad-
dress. Any address from 1-247 may be programed. If 0
pmp bat vmtr sig tnk
Maximum Time/Stroke
0 = Disabled
Figure 53
pmp bat vmtr sig tnk
Alarm to Relay Delay
0 minutes
Select
Enter
Figure 54
pmp bat vmtr sig tnk
Alarm to Callout Dly
0 minutes
Figure 55
pmp bat vmtr sig tnk
MODBUS Address
1 Device Address