Section 13: 7300G System Troubleshooting
How to Use This Section
The recommendations contained in this section should
be used as a preliminary information resource to
remedy operational issues with the NJEX System. It is
important to read all of the definitions and notes prior
to initiating work.
Each sub-section contains a description of the alarm
and non-alarm indicators followed by a step-by-step
trouble shooting proceedure.
For sub-sections containing information on alarms and
non-alarm indicators, keep in mind that alarms will
trigger the alarm relay output, and the red LED light
on the display panel will flash. Non-alarm indicators
will display on the LCD, cause the green LED to flach
on and off and generate an entry in the Sentry reports
but, will not trigger the alarm relay.
For Additional Help
Any issue that can not be resolved through the use of
this reference, please contact YZ Technical Service at:
T: 1.800.653.9435
(1.800.NJEX-HELP)
T: 1.281.362.6500, International Calls
F: 1.281.362.6513
Assistance is available 24 hours a day, 7 days a week,
365 days a year, via the 800 telephone number listed
above.
SAFETY NOTES
• Always use extreme care when performing mainte-
nance on an odorization system. Check to ensure
the removal of liquid odorant and pressure from the
portion of the system on which work will be per-
formed prior to removing components or fittings.
• Inspect all tube fittings and valve packings semi-
annually to ensure that liquid odorant remains within
the system.
Step-by-Step Resolution
Using a step-by-step method to resolve issues on the
NJEX System will reduce maintenance time and assit
in returning the odorization system to service quicker.
The following repesent the recommended chronology
to resolve issues:
1. Complete the Troubleshooting Form located in
Some of the
information entered on the
2. Re-establish the correct pressures.
a. Expansion Tank, 25psi
(1.72 Bar)
b. Bulk Storage Tank, 30-35psi
(2.07-2.41 Bar)
c. Actuation Supply, 75psi
(5.17 Bar)
d. Pump Actuation, refer to
Schematic in Section 2: System Installation
3. Resolve alarm issues to the following order:
a. Tank Level,
page 83
b. Battery,
c. Signal,
d. Verometer,
e. Pump,
Tank Level Alarm
These alarms should only be active with skid mounted
odorizer and tank assemblies furnished pre-assembled
by YZ Systems, Inc. The set points for these alarms are
adjustable in the parameter section of the N-300 control-
ler.
• The
Odor Tank Low Level Alarm
should be set be-
tween 5% to 25%. This alarm indicates a tank level
at or lower that the alarm set point.
• The
Odor Tank High Level Alarm
should be set
between 80% to 90%. This alarm indicates a tank
level at or above the alarm set point.
If your system was not purchased as a skid mounted
assembly with a tank from YZ Systems, this alarm
should be set to disabled in the alarm parameters sec-
tion of the controller.