Section 13: 7300G System Troubleshooting
Verometer Odorant Inlet Low
Alarm Troubleshooting Steps
When an active
OdorInlet Lo
alarm is indicated the
following steps should be taken:
1. Verify that the bulk odorant storage tank pressure
exsits in a range of 30 to 35 psi
(2.07 to 2.41 Bar)
and re-establish the correct pressure if necissary.
2. Inspect the alarm set point programmed into
the N-300 controller and verify that it is correclty
programmed and correct if necessary,
parameters section on programming the N-300
Sections 5 & 6, page 25 or page 33
depending on the mode of operation
.
3. Observe if the alarm is still active, if it is, contact
YZ Technical Services.
Verometer Odorant Inlet Hi
Alarm Troubleshooting Steps
When an active
OdorInlet Hi
alarm is indicated the
following steps should be taken:
1. Verify that the bulk odorant storage tank pressure
exsits in a range of 30 to 35 psi
(2.07 to 2.41 Bar)
and re-establish the correct pressure if necissary.
2. Inspect the alarm set point programmed into
the N-300 controller and verify that it is correclty
programmed and correct if necessary,
parameters section on programming the N-300
Sections 5 & 6, page 25 or page 33
depending on the mode of operation
.
3. Observe if the alarm is still active, if it is, contact
YZ Technical Services.
Verometer Expansion Tank Cable
Alarm Troubleshooting Steps
When an active
XTank-Cable
alarm is indicated the
following steps should be taken:
1. Inspect all cables for any external damage such
as cuts or crimps in the external cable sleeve or
moisture inside the cable connector.
2. Loosen and inspect the cable orientation pins
for correct positioning. All cables have a specific
mating connection to ensure that the correct pins
on the opposing sides of the connector align.
These pins must be correctly aligned to ensure
the electronic signals reach the correct electronic
address in the microprocessor.
3. Reconnect cables as noted above, ensuring that
the alignment pins are mated correctly and that
locking rings are tight. Observe if the alarm is still
active, if it is, contact YZ Technical Services.
Verometer Expansion Tank
Low Alarm Troubleshooting Steps
When an active
XTank Low
alarm is indicated the fol-
lowing steps should be taken:
1. Verify that the expansion tank pressure is at 25
psi
(1.72 Bar)
and correct if necessary.
2. Inspect the alarm set point programmed into
the N-300 controller and verify that it is correclty
programmed and correct if necessary,
refer to the
parameters section on programming the N-300
controller
Sections 5 & 6, page 25 or page 33
depending on the mode of operation
.
3. Observe if the alarm is still active, if it is, contact
YZ Technical Services.