background image

YZ Systems Milton Roy • 201 Ivyland Road • Ivyland, Pennsylvania • USA • 18974 • P: 281.362.6500 • www.yzsystems.com

Page 8

NJEX 610G / 610F  ver.11-2023

Section 3:  Filling the Bulk Odorant Tank 

Filling the Tank for the First Time

CAUTION: 

Odorant has a very strong odor, which if allowed 

to escape into the atmosphere may cause 

problems in the local community. Take necessary 

precautions when filling an odorant storage tank 

to assure that the local community is not 

disrupted during the filling process. Verify that 

the entire system has no pressure in it before 

beginning. Additionally, all personnel should 

wear protective clothing, and use equipment as 

recommended by the chemical manufacturer 

during this time. If you are uncertain about any 

aspect of the odorant itself, you should contact 

the manufacturer of your chemical prior to 

proceeding.

 

The MAXIMUM amount of odorant 

in the standard tank should never exceed 4 

gallons.

1.  Verify correct position of valves before begin-

ning, 

figure 5

.

    Closed: V10, V11 and V13

2.  Attach inert or natural gas supply to V10.

3.  To purge the tank open valve V10 to introduce 

inert or natural gas to the tank to begin dis-

placing any ambient air from the empty tank. 

Continue until pressure on the gage located 

directly below V10 is observed, then partially 

open V11 to allow ambient air from the tank to 

begin flowing out. Allow this process to continue 

until all ambient air from the tank is purged, and 

only inert gas or natural gas is emitting from 

this valve, then close V11 and V10. The time 

required to accomplish this task will vary with 

the tank size.

4.  Vent purge gas by opening V11 partially until 

tank pressure just reaches zero, and then close 

V11.

5.  Attach odorant supply to V10, open V10, and 

begin transferring odorant to the bulk tank.

       •    The tank level indicator will not start to  

    rise until approximately 0.5 gallons of 

      odorant is in the tank.

  •     1 gallon is approximately the thin line  

    above the fitting.

  •     2.5 gallons is approximately the next thick  

    line below the red keep-out.

  •     4 gallons is about where the red diagonal  

    keep-out mark starts.

6.  Connect a line from V11 to a flare or vapor 

recovery device, and open V11.

CAUTION: 

Fill tank to a maximum level of 80% of the tank

capacity (4 gallons). Stay below the red-diagonal 

keep-out.

7.  Close V10 and V11,  and remove odorant 

transfer equipment, and line to flare or vapor 

recovery device.

8.  Continue through the remaining procedures in 

this manual.

Figure 6

Z-100

Analog or Pulse Input

(By Customer)

6000

Pump

Pipeline

V18

V17

NJEX STORAGE TANK

ODORANT  SIGHTGLASS

PROBE ASSEMBLY

(Option)

V8

Actuation Gas

Filter

610G ENCLOSURE

Timer / Controller

V10

V11

V13

S Y S T E M S

Gas Supply

50-60 psi

(345 - 415 kPa)

By Customer

Summary of Contents for NJEX LVO 610G

Page 1: ...NJEX LVO 610G NJEX LVO 610F N A T U R A L G A S O D O R I Z A T I O N S Y S T E M...

Page 2: ......

Page 3: ...NJEX LVO 610G 610F Instruction Operating Manual Version 11 2023...

Page 4: ...m Connections 7 Section 3 Filling the Bulk Odorant Tank 8 Filling the Tank for the First Time 8 Refilling the Bulk Odorant Tank 9 Section 4 System Control Electronics 10 Overview 10 Section 5 Programm...

Page 5: ...tion 7 Mechanical System 24 Overview 24 NJEX LVO Gas Filter 25 Model 6000 pump 26 Flow Switch 27 Section 8 System Maintenance 28 Preventative Maintenance Schedule 28 Recommended Spare Parts List 28 Se...

Page 6: ...ns a hyperlink to the referenced item Items that require action for example the press ing of a key for programming the controller will feature the action item in sentence case Bold Text followed in no...

Page 7: ...ed an external relay contact from external device can be connected to the Inhibit NBS input to inhibit and restart pump operation Proportional to Time Timer Mode Operation In Timer mode the pump is ac...

Page 8: ...System Accessories Odorant Injection Probe includes a 316 stainless steel probe and isolation valve for lo cation at the pipeline When ordering please specify pipeline connection required or Odorant I...

Page 9: ...nd the odorant discharge manifold IP54 rated E NJEX LVO Gas Filter Installed between the actuation gas regulator and the actuation gas manifold this filter provides a 25 micron coalescent filtration t...

Page 10: ...89 13 8 bar 30 psi 2 07 bar 200 500 psi 13 89 34 5 bar 40 psi 2 76 bar 500 900 psi 34 5 62 1 bar 50 psi 3 45 bar 900 1400 psi 62 1 96 5 bar 60 psi 4 14 bar Z 100 Analog or Pulse Input By Customer V13...

Page 11: ...ection of 2 pipe in a vertical configuration at the location where the NJEX LVO 610G NJEX LVO 610F is to be installed Using the mounting clamps provided with the NJEX LVO 610G NJEX LVO 610F system att...

Page 12: ...ring performance To prolong the service of seals and o rings adequate heat should be provided to maintain an operating environment above 32 F 0 C 2 Connect the pump discharge valve fitting to the pipe...

Page 13: ...elow V10 is observed then partially open V11 to allow ambient air from the tank to begin flowing out Allow this process to continue until all ambient air from the tank is purged and only inert gas or...

Page 14: ...ng Figure 6 Closed V10 V11 V13 3 Connect a line from V11 to a flare or vapor recovery device and open V11 4 Attach odorant supply to V10 open V10 and begin transferring odorant to the bulk tank CAUTIO...

Page 15: ...accordance with the Wiring Control Document see Figure 20 The Z 100 rated for use in Class I Division 1 Groups C D and IECEx ATEX Zone 1 hazardous locations WARNING Electrostatic Discharge Hazard Wipe...

Page 16: ...would like to move To open sub menus enter parameters etc you will use the navigation like a push button and push by pressing in the center of the switch When viewing a screen note if there is an arro...

Page 17: ...the navigation switch left for approximately 1 second to start or stop system Bottom left has timer countdown to next pump stroke in counter mode a of accumulated pulses is shown Totalizer From the H...

Page 18: ...ndividually Note the arrow underneath the digit that is currently being edited Press the left or right arrow to change which digit is updated To change the value press the navigation switch up or down...

Page 19: ...ble an indicates the currently selected mode Once a mode has been selected press the left key to exit back to the Mode Menu Timer Mode In timer mode the controller actuates the 6000B pump at a set tim...

Page 20: ...to 1 000V and the Flow Zero Screen will show CALIBRATED indicating that a user calibration value is being used If the flow signal is too far out of range a RANGE ERROR message will be shown and there...

Page 21: ...puts and report system status Flow No Signal The Flow No Signal setting deter mines the percentage of max gas flow the 610G F system will assume as the current pipeline flow when a valid flow signal i...

Page 22: ...seasonal changes the BACK PRESSURE setting should be updated accordingly Density The ODORANT DENSITY setting is used in the cal culations for estimating the mass odorant injected and odorization rate...

Page 23: ...ll have a single line dash next to the alarm Press the navigation switch left to exit the sub menu Battery Low The Battery Low alarm is an indication the battery voltage is low and should be replaced...

Page 24: ...ume odorizing when power is restored system is OFF when power is lost it will remain OFF when power is restored To enable open the Resume on Power Loss sub menu Press navigation switch up or down and...

Page 25: ...Output activity Pump Test and Date Time changes MM100 When ready to download the Z 100 logged data remove the rubber plug located in the opening on the bottom of the Z 100 enclosure and insert the MM...

Page 26: ...nput setting If the REMOTE INHIBIT input setting is ON or NBS upon entry the INHIBIT TEST screen will show the INHIBIT test type INHIBIT ON or INHIBIT NBS with NOTTESTING status Press enter on the nav...

Page 27: ...d the LED will flash GREEN If the battery voltage is found to be low during the test the LED will flash RED A fully charged new battery pack will measure approximately 14 4V if measured with a DMM or...

Page 28: ...b 3 Desired injection rate lb MMCF or mg m c 4 Average flow rate MCF hr or m hr d 5 Timer setting a English a x b x 15 8503 c x d a Metric a x b x 60000 c x d Example 1 Example 2 English Gas Flow Metr...

Page 29: ...0F ver 11 2023 Section 7 Mechanical System Overview The 610G 610F mechanical system is composed of the mechanical electrical enclosure Individual components of the system are shown below and described...

Page 30: ...d 30 60 psi 2 1 4 1 bar per Table 1 Page 5 actuation gas supply provided by the system operator By conditioning the incoming actuation gas a clean pneumatic supply will be provided to the solenoid val...

Page 31: ...rtridge design in key areas that may require maintenance They are the inlet check valve the discharge check valve and the plunger bushing seal assembly The cartridge design provides easier maintenance...

Page 32: ...e factory but may need to be adjusted for the installation site To adjust the flow switch loosen the set screw C and move the reed switch contact B up or down and tighten the set screw On the home scr...

Page 33: ...he odorant and the odorant bulk storage tank and the pump stroke frequency All of these issues must be considered when establishing a preventative maintenance schedule Recommended Maintenance Schedule...

Page 34: ...ssistance is available 24 hours a day 7 days a week 365 days a year via the telephone numbers listed above SAFETY NOTES Always use extreme care when performing maintenance on an odorization system Che...

Page 35: ...be tested with the battery test option under the test menu Navigate to the battery test menu and press enter on the navigation switch While in the battery test menu press the navigation switch in to t...

Page 36: ...d remove the actuation gas line at the top of the pump and test the pump stroke again As the Test key is pressed there should be a burst of gas at the open actuation supply connection If the gas is re...

Page 37: ...rrect as needed 2 Check that the pump is operating as ex pected If the pump is not stroking see the pump troubleshooting section 3 If the pump is functioning as expected go to the Z 100 Controller ter...

Page 38: ...PA U S A 1 8 9 7 4 P 2 8 1 3 6 2 6 5 0 0 w w w y z s y s t e m s c o m Page 33 NJEX 610G 610F ver 11 2023 Appendix A Illustrations NJEX LVO Model 6000B pump Assembled Actuation Gas Actuation Gas Odor...

Page 39: ...o m Page 34 NJEX 610G 610F ver 11 2023 Appendix A Illustrations O Ring P N A5 1013 Actuation Fitting Assembly P N A1 0216 O Ring P N A5 1127 Actuation Seal P N A6 0076 Actuation Spring P N C3 0036 Pi...

Page 40: ...Ring O Ring O Ring P N A5 1117 P N A5 1118 P N B0 1030 Bottom Cartridge P N A6 0091 Secondary Seal P N A6 0090 Seal Support P N A6 0089 Primary Seal P N B0 1033 Stop Bushing CV Inlet Wafer O Ring P N...

Page 41: ...endix A Illustrations Figure 19 Gas Filter Label PN D5 0074 O Ring 334 Viton PN A5 1334 Coalescing Filter Element1 PN C4 0133 Filter Retainer Washer PN C4 0102 Filter Bowl PN C4 0131 In Gas Filter Cap...

Page 42: ...3193094 Z 100 CONTROLLER External I S Supply Ui 28VDC Ii 178mA Pi 1 245W Internal Battery Pack Ui 15 6VDC Ii 299 18mA Pi 1 054W SOLENOID 50mA 12VDC NOMINAL FLOW SWITCH LVO 610F MODELS ONLY SEE WIRING...

Page 43: ...hnical data the export of which is or may be restricted by the Export Administration Act and the Export Administration Regulations EAR 15 C F R parts 730 774 Diversion contrary to U S law is prohibite...

Page 44: ...oy 201 Ivyland Road Ivyland Pennsylvania USA 18974 P 281 362 6500 www yzsystems com NJEX 610G 610F ver 11 2023 201 Ivyland Road Ivyland PA 18974 P 281 362 6500 F 281 362 6513 techsupport yzsystems com...

Reviews: