SECTION 3: FILLING THE BULK ODORANT TANK
YZ Systems Milton Roy • 201 Ivyland Road • Ivyland, PA • USA • 18974 • P: 281.362.6500 • www.yzsystems.com
NJEX ZEO Version 04/13/2021
Page 27
CAUTION: Fill tank to a maximum level of 80% of the tank capacity.
7. Close
V10
and
V11
, and remove odorant transfer equipment, and line to flare or vapor
recovery device.
8. Continue through the remaining procedures in this manual.
Refilling the Bulk Odorant Tank
CAUTION: Fill tank to a maximum level of 80% of the tank capacity.
IMPORTANT: If using an existing NJEX odorant tank, a ¼” NPT tee must be
installed under the regulator to supply the blanket gas to the system. See the P&ID
on page 13 for reference.
CAUTION: Odorant has a very strong odor, which if allowed to escape to the
atmosphere, may cause problems in the local community. Take necessary
precautions when filling an odorant storage tank to assure that the local community
is not disrupted during the filling process. Verify that the entire system has no
pressure in it before beginning.
Additionally,
all personnel should wear protective
clothing, and use equipment as recommended by the chemical manufacturer during
this time. If you are uncertain about any aspect of the odorant itself, you should
contact the manufacturer of your chemical prior to proceeding.
1. Stop the NJEX ZEO system by pressing the Right Arrow Key on the keypad on the N-
400 controller.
2. Verify correct position of valves before beginning.
-
Open:
V12
-
Closed:
V10
,
V11
,
V13
,
V15
3. Connect a line from
V11
to a flare or vapor
recovery device, and open
V11
.
4. Attach odorant supply to
V10
, open
V10
, and
begin transferring odorant to the bulk tank.
CAUTION: Fill tank to a maximum level of 80%
of the tank capacity.
5. Close
V10
and
V11
and remove odorant
transfer equipment, and line to flare or vapor
recovery device.
6. Open
V13
and
V15
.
7. Monitor blanket gas pressure
– allow tank to settle into regulated blanket pressure of
10-25 psi (0.7-1.7 Bar) before continuing.
8. Resume system operation by pressing the Right Arrow Key on the keypad on the N-
400 controller.
Figure 14 Odorant Tank Valves