SECTION 6: TROUBLESHOOTING
YZ Systems Milton Roy • 201 Ivyland Road • Ivyland, PA • USA • 18974 • P: 281.362.6500 • www.yzsystems.com
Page 70
NJEX ZEO Version 04/13/2021
-
Odorant Pressure High
alarm indicates that the odorant pressure has exceeded the
maximum pressure as defined in the set-up parameters in the N-400 controller.
-
Odorant Pressure Cable
alarm indicates that the N-400 controller is no longer receiving
a pressure signal and the cable connection should be verified.
Odorant Pressure Low Alarm Troubleshooting
When an active Odorant Inlet Pressure Low Alarm is indicated, the following steps should be
taken:
1.
Verify the blanket pressure on the bulk odorant tank is in the range of 10
– 25 psi (.68 –
17.2 Bar) and reestablish the correct pressure if applicable.
2.
If the alarm is still active, verify the programmed high and low values in the Set Alarm
Parameters menu.
3.
Recalibrate the Inlet Pressure per the instructions given in Section 5.
4.
If the alarm is still active, please contact YZ Technical Services for additional assistance.
Odorant Pressure High Alarm Troubleshooting
When an active Odorant Inlet Pressure High Alarm is indicated, the following steps should be
taken:
1.
Verify the blanket pressure on the bulk odorant tank is in the range of 10
– 25 psi (.68 –
17.2 Bar) and reestablish the correct pressure if applicable.
2.
If the alarm is still active, verify the programmed high and low values in the Set Alarm
Parameters menu.
3.
Recalibrate the Inlet Pressure per the instructions given in Section 5.
4.
If the alarm is still active, please contact YZ Technical Services for additional assistance.
Odorant Pressure Cable Alarm Troubleshooting
When an active Odorant Pressure Cable Alarm is indicated, the following steps should be taken:
1.
Inspect all cables for any external damage such as cuts or crimps in the external cable
sleeve or moisture inside the cable connector.
2.
Loosen and reinstall the cable in the controller. Inspect pluggable terminal block for
damage and replace if necessary.
3.
Observe if the alarm is still active, if it is, contact YZ Technical Services.
Injection Pump Alarms
There are two Injection Pump alarms monitored by the N-400 Controller to ensure correct and
safe operation of the NJEX ZEO System. The alarms relating to the Injection Pump and their
description is as follows: