SECTION 1: THINGS TO KNOW - NJEX ZEO
YZ Systems Milton Roy • 201 Ivyland Road • Ivyland, PA • USA • 18974 • P: 281.362.6500 • www.yzsystems.com
Page 6
NJEX ZEO Version 04/13/2021
System Certifications
The NJEX ZEO System holds one of the following approvals and must be installed, grounded,
wired, and I.S. Barrier Protected in accordance with all applicable electrical codes:
In addition to local electrical codes for which the system is installed, the systems must also
comply with the
located in the appendix of this manual. For both
hazardous location listings, the
N-400 Wiring Control Document 1E-0378
any connections to the N-400 controller. See the system level Wiring Control Documents
for requirements for connecting incoming power per the hazardous location
listing.
North America, Class and Division Hazardous Location*
Class 1, Division 1, Groups C and D
Class 1, Zone 1, Group IIB
T3C
Type 3R
*WARNING: To comply with the North American hazardous location requirements and
to reduce the risk of ignition of hazardous atmospheres, conduit runs must have a
sealing fitting (not provided) connected within 18 inches of the enclosure.
ATEX, IECEx Zone Hazardous Location
IECEx ETL 20.0051X
Ex db ia [ia IIC Ga] IIB T4 Gb
ITS21UKEX0038X
ITS-I21ATEX29212X
II 2 G Ex db ia [ia IIC Ga] IIB T4 Gb
2812
0891
-20°
C ≤ Ta ≤ + 50°C
IP43
Specific Conditions of Use
1. External non-metallic materials represent a potential electrostatic charging hazard. See
the safety notes in this manual for details.
2. The flameproof joints are not intended to be repaired in the Actuator Capacity Control
(ACC). For repair of flameproof joints, see the manufacturer for more information.
3. To guarantee the tensile strength of the screws of the flameproof junction box present in
the Actuator Capacity Control (ACC) and flameproof enclosure, the supplied screws have
a tensile strength of equal to or greater than 700 N/mm
2
. Fasteners are factory supplied.
4. The property class of the special fasteners used in the Elnor Motors (Transfer Pump and
Injection Pump Motors) must be at least: Hexagon cap screws [4.6], Hexagon nut [5] (if
used), Socket Cap Screws [8.8]. Fasteners are factory supplied.