Settings
View the current settings on the N-300 or N-400 controller. The message at the top will state “Setting
Changes Available” when the unit is stopped and “Stop system to make changes” if the system is
running. Unit must be stopped in order to make changes. In order to update parameters users must be
ADMIN level or higher, USER level cannot update parameters.
To update a parameter:
1.
Stop the odorizer
2.
Adjust the parameter
3.
Press
icon on the right side for that parameter
4.
Press
at the bottom (N-300 ONLY)
5.
Press
at the top to confirm that the change was made
Settings (Admin level or above - read/write access):
User Settings (User level - read only access):