STARTING
1. Drain any water in the fuel tank (when
necessary) and fill with oil
2. Check overflow protection – push down
and ensure the level returns to position
and there is a ‘click’
3. Open the top of the heater and remove
all accessible components and clean
thoroughly
4. Check the burner pipe from the oil feed
line is pushed fully into the combustion
chamber
5. Plug into the power supply
6. Ensuring the heater is cool, pour 250
ml of heating oil or diesel into the pan
7. Light the oil with paper or rag
8. Reassemble the ring, deflector and
cylinder
9. Close the lid of the heater
10. Press the “START” button
11. After 10 – 20 minutes the activation
thermostat will start the blower fan,
combustion fan and oil pump. The heater
will automatically run initially on low setting
12. After 30 minutes the heater will
automatically revert to the output level set
on the power output control and you will
be able to vary this
STOPPING
Press the “STOP” button on the control
panel. The pump will stop and the green
LEDs will turn off. The fan will continue to
operate until the heater has cooled down
to below the activation temperature.
SAFETY CUT-OUT & RESET
The heater will stop as above if either the
overheat thermostat or overflow switch are
triggered.
To clear the overheating signal and return
to normal operation, wait until the furnace
is cooled down and the fan is switched off
then press the push-button overheat
thermostat to reset.
Press “STOP” to turn off the LED
signalling ‘overheat’ and then start as
normal.
To restart after overflow, ensure the
heater has fully cooled and clear up any
excess oil in or around the chamber. Then
empty the overflow catch pan and press
“STOP” to turn off the LED signalling
‘overflow’ and then restart as normal.
WARNING
Never
attempt to add oil directly into the
chamber or relight whilst the heater is still
hot. Vapours may cause explosion or
burns. Wait for the heater to fully cool
down first.
Never
try turn off the power to stop the
heater. Use the “STOP” button so the
heater can cycle through it’s cool down
process. Remember the vaporising pan
and other parts will stay hot after the
heater has been switched off.
MAINTENANCE
DAILLY
•
Clean the combustion chamber
and all internal parts
•
Check the oil overflow drain point
is clear
WEEKLY
•
Clean the combustion chamber
base
•
Check the combustion chamber air
inlet holes are clear
•
Check and clean the oil feed line
and pipe
MONTHLY
•
Clean the fuel tank and check oil
pump filter