background image

PCP - 04 TIME RELAY 

INSTRUCTION MANUAL

Zakład Mechaniki i Elektroniki 

ZAMEL 

sp.j.

J.W. Dzida, K. Łodzińska

ul. Zielona 27, 43-200 Pszczyna, Poland

Tel. +48 (32) 210 46 65, Fax +48 (32) 210 80 04

www.zamelcet.com, 

e-mail:

 marketing@zamel.pl

APPERANCE

FEATURES

DESCRIPTION 

ی  8 operating modes,

ی  Relay state and time counting indica

-

tor – LED,

ی  Triggered by means of power supply 

voltage or control input in dependence 

of set operating mode,

ی  High accuracy of time measure,

ی  Relay  output – one changeover 

contact, 5 A maximum load,

ی  Casing designed for mounting in 

 

a junction box.

The  PCP-04  multifunction  relay  is  de

-

signed for timing function implementation 

in automatics and  control systems. Both 

power  supply  voltage  and  control  input 

trigger  the  relay.    The  PCP-04  relay  is 

capable of operating in 8 independent op 

modes which may be triggered by means 

of either power supply voltage or external 

trigger impulse (from either L or N wires). 

It  is  possible  to  adjust  time  within  very 

wide range. The device is fitted with the 

relay state indicator – the LED.  It is pos

-

sible to mount the device in the 60 mm 

junction box.

TECHNICAL DATA

PCP- 04

Power terminals: L (black), N (blue)

Rated voltage: 230 V

~

Rated voltage tolerance: -15 ÷ +10 %

Rated frequency: 50 / 60 Hz

Rated current:  15,5 mA

External trigger terminal: IN (triggered from L or N line) 

Trigger current: 510 μA

Op modes quantity:

8

t time adjustment range: 0,1 s ÷ 10 days (servo + continuous)

Time measure accuracy: 0,2 %

Relay state and time measure indicator:

red LED

Relay contacts parameters: 1NO5 A / 250 V AC1 1250 VA (voltage contact)

Connection terminals / leads quantity:

4

Connection wire section: 1 mm

2

Operating temperature: -20 ÷ +60 

o

C

Operating position: optional

Casing fastening: 60 mm junction box

Casing IP: IP20 (PN-EN 60529)

Protection class:

II

Overvoltage category:

II

Pollution level: 2

Dimensions: 50 x 50 x 15  mm

Weight: 30 g

Standard conformity: PN-EN 60730-1

PN-EN 60730-2-7

PN-EN 61000-4-2,3,4,5,6,11

Load / time measure indicator

Load power supply lead (P)
Power lead (L)
Operating mode selection

Trigger lead (IN)

ON-time setting

Time range selection

Power lead (N)

b

r

o

w

n

r

ed

b

l

a

ck

b

l

ue

The  timer  should  be 
connected  to  a  single-
phase  system  accordin

-

gly to current standards.
The  device  connections 
will be described  in this 

manual.  Only  qualified  electricians  are 
allowed  to assembly, connect and ad

-

just the timer. It is necessary to read this 
manual  before  the  timer  mounting.  Do 
not disassembly the timer casing or you 
will lose any warranty rights and expo

-

se yourself to the electric shock hazard. 
Before  mounting  operation  make  sure 
of  disconnecting  the  connection  wires  
from  the  electric  network.    The  timer 
should  be  carried,  stored  and  used  in 
an appropriate way.  Do not mount the 
timer  in  case  of  any  device  parts  lack, 
damage or deformation. In case of mal

-

function please notify the manufacturer.

CAUTION

Reviews: