ASSEMBLY

CONNECTIONS

CASING DIMENSIONS

PRODUCT FAMILY

The PCP-04 time relay is a member 

of the PCX product family.

1.  Disconnect the electric network by 

means of an appropriate cut-off, 

current-limiting circuit-breaker or 

separator.

2.  Check if there is no any voltage 

between power leads by means of 

an appropriate gauge.

3.  Mount the 

PCP-04

 device in the 60 

mm junction box.

4.  Connect wires according the electri

-

cal diagram.

5.  Connect power supply circuit.
6.  Select the op mode by means of the 

MODE

 switch.

7.  Select  time  by  means  of  the 

TIME

 

handwheel and the 

RANGE

 switch, 

where 

t

 = 

TIME x RANGE

.

OPERATION

LOAD

Power supply voltage trigger:

U

A

t

t

DELAYED  SWITCH-ON  – 

t

  time  will  be  measured  after  power  supply 

voltage has been switched ON. When the 

t

 time is over, the relay will 

be ON. The op mode will be triggered again after power supply voltage 

switching OFF and ON again.

U

t

t

B

DELAYED SWITCH-OFF – the relay will be ON just after power supply 

voltage switching ON and the 

t

 time will be measured. When the 

t

 time 

is over the relay will be OFF. The operating mode will be triggered again 

after power supply voltage switching OFF and ON again.

U

t

t

t

t

t

t

C

CYCLIC SWITCHING (starts from the OFF state) – 

t

 time will be measured 

after power supply voltage has been switched ON. When the 

t

 time is over, the 

relay is ON. Then the relay will be switched alternatively in 

t

 time cycles. The 

operating mode will be OFF when power supply is OFF.

External impulse trigger:

S

D

t

t

TIME IMPULSE TRIGGERED WITH RISING EDGE – when supplied, the 

module will switch ON the relay when trigger impulse rising edge comes. 

Then the preset time will be measured. When 

t

 time is over, the relay will 

be OFF. Trigger impulse duration is irrelevant.

S

t

t

E

TIME IMPULSE TRIGGERED WITH TRAILING EDGE – when supplied, 

the module will switch ON the relay when trigger impulse trailing edge 

comes. Then the preset time will be measured. When 

t

 time is over, the 

relay will be OFF. Successive trigger impulse decays during 

t

 time dura

-

tion will not cause time counting reset (non-retriggerable circuit).

S

t

t

F

t

t

t

DELAYED SWITCHING ON / OFF – when supplied, the module will not 

switch ON the relay and will start 

t

 time measure when trigger impulse 

rising edge comes. When t time is over, the relay will be ON 

t

 time will be 

counted once again when trigger impulse trailing edge comes. When 

t

 

time is over, the relay will be OFF. If the impulse duration is shorter than 

t

 time, the relay will be ON for 

t

 time only.

S

t

t

G

t

BISTABLE RELAY WITH TIME LIMIT – when supplied, the module will 

switch ON the relay and start 

t

 time measure when trigger impulse rising 

edge comes. The relay will be switched OFF when the next trigger impul

-

se rising edge comes or after 

t

 time has been over if the trigger impulse do 

not come. The impulse duration is irrelevant for the circuit operation.

S

H

t

t

t

t

t

TIME  IMPULSE  TRIGGERED  WITH  RISING  EDGE  WITH  DELAYED 

SWITCH OFF (retrigerrable) – when supplied, the module will switch ON 

the relay when trigger impulse rising edge comes. When trigger impulse 

trailing edge comes, 

t

 time will be measured and when the time is over, the 

relay will be OFF. Successive trigger impulse trailing edge will cause 

t

 time 

counting reset and measure from the beginning (retrigerrable).

Multiplier:

0,1 s                                       1 s                                           10 s                                         1min.

10 min.                                   1 hour                                    10 hours                                  1day

MODE

MODE

MODE

MODE

MODE

MODE

MODE

MODE

RANGE

RANGE

RANGE

RANGE

RANGE

RANGE

RANGE

RANGE

375 W 

               180 W

90 W 

               150 W

L/N

b

r

o

w

n

red

b

la

ck

b

lue

24 VAC/DC power supply

Device version:

01 - mode: delayed ON
02 - mode: delayed OFF
03 - mode: cyclic changeover
04 - few op modes
10 - 10 modes,two periods
       adjustment

Casing type:

M - single-module
     (double-module for 10 ver.)
P - for junction box

Device type

WARRANTY

The product warranty is for a period of 24 months

Dealer signature & stamp, purchase date

1. ZMIE ZAMEL SP. J. assures 24 months guarantee for the product.

2. The manufacturer’s guarantee does not cover any of the following actions:

a) mechanical damage during transport, loading / unloading or under other circumstances,

b) damage caused by incorrect product mounting or misuse,

c) damage caused by unauthorised modifications made by the PURCHASER or any third parties to the product or any other devices 

needed for the product  functioning,

d)  damage caused by Act of God or any other incidents independent of the manufacturer.

3. The PURCHASER shall lay any claims in writing to the dealer or ZMIE ZAMEL SP. J.

4. ZMIE ZAMEL SP. J. is liable for processing any claim according to current Polish legislation.

5. ZMIE ZAMEL SP. J. shall process the claim at its own discretion: product repair, replacement  or money return. 

6. The manufacturer’s guarantee is valid in the Republic of Poland.

7. The PURCHASER’s  statutory rights in any applicable legislation whether against the retailer arising from the purchase contract or 

otherwise are not affected by this warranty.