Safety parameters according to EN ISO 13849-1
Safety parameters according to IEC 61508 - High-Demand - Request Rate < 1 year
Safety parameters according to IEC 61508 - Low-Demand - Request Rate
≥
1 year
Conditions:
AC-15: 5 A; Max. 10.000 Switching-Cycles / Year
DC-13: 4 A; Max. 15.000 Switching-Cycles / Year
Max. duration of use [Years]
20
Category
4
PL
e
PFHd [1/h]
1.2E-08
Conditions:
AC-15: 5 A; Max. 10.000 Switching-Cycles / Year
DC-13: 4 A; Max. 15.000 Switching-Cycles / Year
Max. duration of use [Years]
20
Proof-Test-Intervall [Years]
20
PFH [1/h]
1.2E-10
SIL
3
Conditions:
AC-15: 5 A
DC-13: 4 A
Max. duration of use [Years]
20
Proof-Test-Intervall [Years]
9
PFD
AVG
9.87E-05
SIL
3