Safety Time Control Device
20. Technical data
Electrical data
Operating voltage
U
B
: DC 24 V
Voltage tolerance
+ 10 % / - 15 %
Power consumption
(no load) at U
B
3.6 W
Display
2-digit x 7-segment LED display; 3 LEDs
Power-on delay
9 s
Two-channel safety inputs
Number
1
Input current at high level
Type 7 mA
Galvanic isolation
no
Low level
min: 0 V; max: 5 V
High level
min: 18 V; max: U
B
Max. Switch on delay
800 ms
(+ configured delay times, if applicable )
Max. switching frequency
0,8 Hz
Start input/ feedback circuit
Number
per 1
Function
X1:Auto start / monitored manual start
(depending on configuration)
Y1: Monitoring of external contactors or expansion
modules
Input current at high level
Typ. 7 mA
Galvanic isolation
no
Low level
min: 0 V; max: 5 V
High level
min: 18 V; max: U
B
Max. Time between I11 and I12
3 seconds
Safety characteristics for alternate 1oo1 structure for process industy - High Demand
Conditions:
Day of operation/year: 365; Hours/Day: 24; Switching-Cycle/Hour: 0,5; Maximum load AC-15/DC-13
Relay
Semiconductor output
Device type
B
B
HFT
0
0
SIL
3
3
SFF
[%]
99,92
99,92
λ
SD
[FIT]
0,00
0
λ
SU
[FIT]
458,57
292,96
λ
DD
[FIT]
40,96
25,18
λ
DU
[FIT]
0,41
0,25
PFH
D
4,10E-10
2,52E-10
Safety characteristics for alternate 1oo1 structure for process industy - Low Demand
Relay
Semiconductor output
Gerätetyp
B
B
HFT
0
0
SIL
2
3
SFF
[%]
98,01
99,91
λ
SD
[FIT]
0,00
0,00
λ
SU
[FIT]
292,08
290,43
λ
DD
[FIT]
0
0,00
λ
DU
[FIT]
5,92
0,25
PFD
avg
(z.B. für T = 1 Jahr)
2,59E-05
1,11E-06