AE0ZP0EC - AC-0 SSL SENSORED - User Manual
Page - 47/100
10.5).
12) THROTTLE X POINT
This parameter, together with the THROTTLE Y POINT, changes the
characteristic of the accelerator input curve (see also paragraph 10.5): when
the accelerator is de-pressed to X point per cent, the corresponding truck
speed is Y point per cent of the Maximum truck speed. The relationship
between the accelerator position and the truck speed is linear between the
THROTTLE 0 ZONE and the X point and also between the X point and the
maximum accelerator position but with two different slope (see also Figure
10–2).
13) THROTTLE Y POINT
This parameter, together with the THROTTLE X POINT, changes the
characteristic of the accelerator input curve (see also paragraph 10.5): when
the accelerator is de-pressed to X point per cent, the corresponding truck
speed is Y point per cent of the Maximum truck speed. The relationship
between the accelerator position and the truck speed is linear between the
THROTTLE 0 ZONE and the X point and also between the X point and the
maximum accelerator position but with two different slope (see also Figure
10–2).
14) ADJUSTMENT #01
It adjusts the upper level of the battery charge table (Level 0 to 9). See
paragraph 10.6.
15) ADJUSTMENT #02
It adjusts the lower level of the battery charge table (Level 0 to 9). See
paragraph 10.6.
16) LOAD HM FROM MDI
When set On, the HourMeter of the Controller is transferred and recorded on
the HourMeter of the Standard MDI (connected on the Serial Link).
17) CHECK UP DONE
Turn it On when the asked Maintenance service has been executed to cancel
the CHECK UP NEEDED warning.
18) CHECK UP TYPE
It specifies the handling of the CHECK UP NEEDED warning:
-
NONE:
No CHECK UP NEEDED warning
-
OPTION #1: CHECK UP NEEDED warning on the hand set and MDI-
PRC after 300 hours
-
OPTION #2: Equal to OPTION#1 but Speed reduction after 340 hours
-
OPTION #3: Equal to OPTION#2 but the truck definitively stops after
380 hours
19) OPTION 05
(MDI-PRC version only). This setting, together with the four settings below,
specifies an offset for the MDI-PRC HourMeter. The MDI-PRC HourMeter will
be the sum of the Controller HourMeter plus this offset. This offset value is 5
Digits with:
-
OPTION 05 is the MSDigit
-
OPTION 01 is the LSDigit
It is possible to change this offset only when the controller HourMeter is less