User’s Manual 1PH HYD3000-HYD6000-ZP1
Rev. 1.0 01/09/2023
Identification: MD-AL-GI-00
Rev. 1.1 of 27/01/2023 - Application: GID
180/193
15.5.3.
Checking that the datalogger has been configured correctly
Wait two minutes after completing the configuration of the device.
First of all, check that the LINK LED on the device is on and steady.
Figure 121
– LED indicating the correct configuration of the datalogger
Enter the IP address 10.10.100.254 again, and the login credentials (“admin” for both username and
password). Once logged in, the Status screen will appear, where the following information can be checked:
•
Check Wireless STA mode (if the datalogger has been configured via Wi-Fi)
-
Router SSID > Router name
-
Signal Quality > other than 0%
-
IP address > other than 0.0.0.0
•
Check Cable mode (if the datalogger has been configured via Ethernet cable)
-
IP address > other than 0.0.0.0
•
Check Remote server information
-
Remote server A > Pingable