Identification: MD-AL-GI-00
Rev. 1.2 07.06.21 - Application: GID
Connext User Manual
Rev. 2.2 10/01/2023
Figure 29 - RS485 connections with single-phase string inverter
Figure 30
–
Connection of exchange sensor on Connext
The CT must be positioned according to the diagram shown in
. Then check the direction of the current measured by the CT. Procedure:
-
Photovoltaic system switched OFF
-
Loads switched ON (e.g. oven, hairdryer, etc.)
Power from the grid must be negative (i.e. withdrawal) If this is not the case, change the direction
of the CT.