18 - EN
6.2 Ventilation time clock (M60)
The unit can also be controlled automatically by a
built-in timer. To ensure the timer works properly, the
correct time must be set first in parameter M60-01
and M60-2. When setting parameter M60-04 to “1”
the unit will automatically adjust for Daylight Saving
Time.
Function
Parameter
Real time
M60-01
Real date
M60-02
Daylight Saving Time automatic
M60-04
In parameter M60 six switching moments can be set
for the timer.
Not all switching moments need to be
programmed.
Function
Parameter
Switch moment 1
M60-1x
Switch moment 2
M60-2x
Switch moment 3
M60-3x
Switch moment 4
M60-4x
Switch moment 5
M60-5x
Switch moment 6
M60-6x
For each switch moment three parameters must
be set. In the 1st parameter (M60-x1), the required
switch time must be entered.
In the 2nd parameter (M60-x2), the required switch
day or days must be selected. As default all 2nd
parameters (M60-x2) are set to “0” (Never), this way
the unit will not respond to the timer.
In the 3rd parameter (M60-x3), the required
ventilation speed must be entered.
Function
Parameter
Switching time
M60-x1
Switching day
M60-x2
Ventilation speed
M60-x3
Switching day(s) in M60-x2
Option
Never
0
Every day
1
Weekday mon..fri
2
Weekend sat+sun
3
Monday
4
Tuesday
5
Wednesday
6
Thursday
7
Friday
8
Saturday
9
Sunday
10
Ventilation speed in M60-x3
Option
M02-10 = 0: Ventilation off
M02-10 ≠ 0: First setpoint
0
M02-10 = 0: Ventilation speed1
M02-10 ≠ 0: First setpoint
1
M02-10 = 0: Ventilation speed2
M02-10 ≠ 0: First setpoint
2
M02-10 = 0: Ventilation speed3
M02-10 ≠ 0: First setpoint
3
M02-10 = 0: Ventilation speed4
M02-10 ≠ 0: First setpoint
4
M02-10 = 0: Ventilation speed4
M02-10 ≠ 0: Second setpoint
5
In parameter M60-03 the current requested
ventilation speed by the ventilation time clock is
displayed.
With the “Enable time clock” function it is possible
to switch off the ventilation time clock function with
an installed switch. (see chapters about manually
switching functions off)
The clock works on a battery. When the battery is
empty or the clock is broken, the unit will display
error E04 or E05