4.4 Configuration Main PCB
A
C
D
E
F
G
H
B
K
I
H
N
M
O
P
Q
L
J
#
Description
Specification
A
Supply voltage connection.
Power
230 V
B
2 power relay outputs.
Power
230 VAC
Maximum current
8 A
C
Pressure sensor for supply flow calculation.
-
-
D
Pressure sensor for exhaust flow calculation.
-
-
E
2 analogue outputs.
Impedance
10 Ω
Minimum load resistance
Maximum current
5 kΩ
5 mA
F
3 digital inputs.
Maximum terminal resistance
(detection closed)
150 Ω
Maximum current
1 mA
G
Type B USB communications connector.
-
-
H
4 operating push buttons.
-
-
I
LCD two-line display.
-
-
J
SD slot.
Check whether the SD-card used is not locked and can be overwritten.
Size
Type
≥ 4GB
SD/HC
K
6 temperature inputs.
-
-
L
RJ45 communications connector for linking to the connector PCB.
-
-
M
Pressure sensor for supply dirty filter alert.
-
-
N
Pressure sensor for extract dirty filter alert.
-
-
O
Slow-blow fuse.
Type
315mAT
P
5 communication ports.
-
-
Q
Button cell.
Type
CR2032 Li-Mn 3V