EN - 30 - For the installer
3.8 Programming air specifi cations
After installation, the ComfoAir must be programmed.
This can be done using the air specifi cations of the
ComfoAir above.
The default settings of the ComfoAir, nL, are:
Position A
BSENT
15%
Position L
OW
35%
Position M
EDIUM
50%
Position H
IGH
70%
The default settings of the ComfoAir, HL, are:
Position A
BSENT
15%
Position L
OW
40%
Position M
EDIUM
70%
Position H
IGH
90%
Follow this procedure to programme the ComfoAir
(after installation):
1.
Set the ComfoAir in programming mode.
–
Display: Press simultaneously for 3 seconds on
"
" and "
" until “InR” appears on the
display.
–
CC Ease panel: Press simultaneously for 3
seconds on "
" and "
" until “InR” ap-
pears on the CC Ease panel.
In programming mode, the bypass and pre-
heater valves are always closed. After 30
minutes, the ComfoAir automatically termi-
nates the programming mode.
2. Close all windows and outside doors.
3. Close all inside doors.
4. Check whether both fans function in the three
speed settings.
5. Switch the ComfoAir to high speed.
6. Install all valves and set the valves according to
the settings.
7. Change the fan settings in P menus P30 to P37 of
the digital operating device.
–
Sele
ct the lowest possible setting in order to
conserve energy.
–
Ensure that the ratios between low, medium
and high remain equal.
Use the chart of the ComfoAir's air specifi ca-
tions to set the fans.
9. In the event that the currently set air volumes still
deviate too much:
– Adjust the valves.
10. Check the entire installation again, after all valves
have been set.