Bypass (M06, M07, M11-01)
All units are equipped with a bypass. The relay,
analog output and position settings for the bypass
are determined by the installed type of bypass.
Never change the relay, analog output and position
settings of the bypass.
Heat exchanger (M12-01)
All units are equipped with a heat exchanger. The
settings for the heat exchanger are determined by
the installed type of heat exchanger. Never change
the settings of the heat exchanger.
Damper (M06)
Some units are equipped with one or two dampers.
The relay settings for these dampers are determined
by the installed type of damper. Never change the
relay settings of the dampers.
Battery (M50)
Some heater/change-over batteries are equipped
with a frost protection. The digital (temperature)
input settings for this frost protection is determined
by the installed type of frost protection. Never
change the digital (temperature) input settings of the
frost protection.
Pre heater (M13)
The location of an installed pre heater determined
which location setting is activated. Never change the
location settings of the pre heater.
6.21 Parameters
M1 – Actual Controls
Parameter
Description
Unit
M01-01
Temperature NTC1
(ODA = outdoor air temperature)
°C
M01-02
Temperature NTC2
(SUP = supply air temperature after the heat exchanger)
°C
M01-03
Temperature NTC3
(ETA = extract air temperature)
°C
M01-04
Temperature NTC4
(EHA = exhaust air temperature)
°C
M01-05
Temperature NTC5
(= supply air temperature after the cooler/heater).
°C
M01-06
Temperature NTC6
(= reserve temperature sensor on the main PCB).
°C
M01-07
Temperature NTC7
(= reserve temperature sensor on the connector PCB).
°C
M01-08
Request Supply air
m3/h
M01-09
Request Exhaust air
m3/h
M01-10
Actual Supply air
m3/h
M01-11
Actual Exhaust air
m3/h
M01-12
Control Supply fan
%
M01-13
Control Exhaust fan
%
M01-14
Pressure Supply nozzle
Pa
M01-15
Pressure Exhaust nozzle
Pa
M01-16
Pressure Supply filter
Pa
M01-17
Pressure Exhaust filter
Pa
M01-18
Request ventilation
%
M01-19
n/a
%
M01-20
n/a
%
M01-21
Actual bypass state
%
M01-22
Actual PreHeater control ODA (= supply air)
%
M01-23
Actual PreHeater control ETA (= extract air)
%
Temperature sensors that are not present return a default value of -30°C.