M10 – Temp Control
Parameter
Description
Unit
M10-01
Controlmode supply temp.
�
0 : Tcomfort (T5 controlled with (Tcomfort-T3) );
�
1 : Outdoor heatline (T5 controlled with M10-02..16).
-
M10-02
TH(low) outdoortemp ,low point outdoor temp. heating
°C
M10-03
TH(low) supplytemp ,low point supplytemp heating
°C
M10-04
TH(med) outdoortemp, medium point outdoortemp heating
°C
M10-05
TH(med) supplytemp,medium point supplytemp heating
°C
M10-06
TH(hi) outdoortemp, high point outdoortemp heating
°C
M10-07
TH(hi) supplytemp, high point supplytemp heating
°C
M10-11
TC(low) outdoortemp, low point outdoor temp. cooling
°C
M10-12
TC(low) supplytemp, low point supplytemp cooling
°C
M10-13
TC(med) outdoortemp, medium point outdoortemp cooling
°C
M10-14
TC(med) supplytemp, medium point supplytemp cooling
°C
M10-15
TC(hi) outdoortemp, high point outdoortemp cooling
°C
M10-16
TC(hi) supplytemp , high point supplytemp cooling
°C
M10-20
Heating P-zone
°C
M10-21
Heating I-time
sec
M10-22
P-zone
°C
M10-23
Cooling I-time
sec
M10-24
Minimum supply temperature T2
°C
M10-25
Maximum supply temperature T2
°C
M10-26
Tsupply request heatline (calculated on M10-02..16 and M10-25)
°C
M10-27
Minimal time between Heating->Cooling
min
M10-28
ΔT heat/cool failure (see failure E38/E39)
�
0 : not active.
°C
M10-29
Minimal supply temp (ALARM)
°C
M10-99
Comfort Temperature (indoor temperature)
°C
M11 – Bypass settings
Parameter
Description
Unit
M11-01
Bypass position:
�
0: Exhaust;
�
1: Exhaust, modulated;
�
2: Supply;
�
3: Supply, modulated;
�
4: Supply, modulated (frost).
Do not change.
n/a
M11-02
Setpoint exhaust temp T4 (frost)
°C
M11-03
P-zone bypass (frost)
°C
M11-04
I-time bypass (frost)
sec
M11-05
Minimal supply temp T2 (frost)
°C
M11-06
Minimal supply temp T5 (frost)
°C
M11-07
Frost protection T1 <
°C
M12 – Heat Exchanger settings
Parameter
Description
Unit
M12-01
Heat Exchanger
�
0: n/a;
�
1: Yes.
Do not change.
n/a
M12-02
Frost setpoint start (supply air volume starts to decrease)
°C
M12-03
Frost setpoint full (supply air is switched off)
°C
M12-04
Balance ventilation (frost)
�
0: No;
�
1: Yes.
n/a