6 - EN
Checking the delivery
Contact your supplier immediately in case of damage
or an incomplete delivery. The delivery should at
least include:
�
The unit; Check the identification plate to ensure
that it is the required type.
�
Seal cap, seal plug, cable feed in packaging;
�
Hoisting instructions (attached to the operating
side);
�
Documentation.
The unit can be supplied in the following sizes:
ComfoAir 800
ComfoAir 3300
ComfoAir 1500
ComfoAir 4400
ComfoAir 2200
ComfoAir 6000
Meaning of the suffixes found on the
identification plate:
Suffix
Explanation
ComfoAir XL
ComfoAir Eco
Product family name
2200
Product type name (air
volumes in m3/h)
CFE
The unit has a counterflow
plate exchanger installed as
default.
A
The unit has a modulated frost
bypass installed in the outdoor
air as default.
L
The unit is a left-hand version.
(Exhaust/Supply Left)
R
The unit is a right-hand
version. (Exhaust/Supply
Right)
B
The unit has an open/close
bypass installed as default.
BM
The unit has a modulating
bypass installed as default.
I
The unit is suitable for indoor
installation;
O
The unit is suitable for outdoor
installation;
PF
The unit has a panel filter
installed as default.
BF
The unit has a bag filter
installed as default.
CL
The unit has a cooler installed
as default.
PRH
The unit has a pre heater
installed as default.
POH
The unit has an postheater
installed as default.
DMP ODA
The unit has an outdoor air
damper installed as default
DMP EHA
The unit has an exhaust air
damper installed as default
The identification plate detailing information on the
unit can be found on the operating side of the unit.
Suffixes between brackets mean there is space
reserved for installing the specified function.
3. Installation conditions
In order to determine whether the unit can be
installed in a certain area, the following aspects
must be taken into account:
�
Check whether the admissible load (kg/m2) of the
roof or floor is sufficient to bear the given weight
of the unit;
�
The system must be fitted to allow sufficient
room around the unit for the air duct connections,
condensation drain as well as for carrying out
maintenance activities like a filter exchange;
To ensure components can be replaced, at least
one casing‘s width of free space is required.
�
The condensation must be drained off frost-free,
at a gradient and incorporate an air seal (U-bend
or dry siphon);
�
The room must offer the following provisions:
- Air duct connections;
- Electrical power connection;
- Provisions for the condensation drain;
- Facilities for battery or batteries.
4. Technical specifications
The units specific technical specifications are added
separately to the unit. This can includes the following
information:
�
Dimension sketch;
�
Wiring diagram;
�
Air specifications;
�
Parameter list with Factory settings.
All general technical information can be found in this
document.
4.1 NTC sensors
The unit has 7 analogue temperature inputs.
The first 5 temperature inputs have a preset function.
The function of temperature sensors 6 and 7 can
be set (parameter M50). Only NTC sensors can be
connected to these inputs.
The resistance of the NTC sensors in the unit are as
follows:
Temperature
Resisitance [kΩ]
[ºC]
MIN.
MED.
MAX.
10
19.570
19.904
20.242
15
15.485
15.712
15.941
18
13.502
13.681
13.861
19
12.906
13.071
13.237
20
12339
12.491
12.644
21
11.801
11.941
12.082
22
11.291
11.420
11.550
25
9.900
10.000
10.100
30
7.959
8.057
8.155