3  Control unit

3.1 Controller

ComfoAir XL is equipped with a multifunctional 
controller. The control unit comprises two different 
PCBs. The main board, to which all internal 
components can be connected, is located inside the 
unit. All external functions are bundled at the 
connection PCB. This is located behind the designer 
front panel and is easily accessible to implement 
numerous connections. The units have an automatic 
frost-protection.

Essential features:

■ 

Connection to the building technology via ModBus communication  

■ 

Constant Air Flow: to set fixed capacities  

■ 

Filter monitoring: Pressure sensors measure the resistance via the filter

■ 

The unit software is equipped with a timeswitch as standard 

■ 

Control via external sensor: CO

2

, pressure, relative air humidity

■ 

Various connections: 230 V, power relay   

■ 

Generation of summer night cooling via digital input 

■ 

Compatible with fire alarm system via digital input

■ 

Summer night cooling: activation via an external signal

■ 

Frost protection for the high-performance plate heat exchanger:  
the supply fan is shut down when there is a risk of frost

ComfoAir XL is easy to change over from constant air 
volume control to pressure control. This type of 
control requires a pressure sensor to measure the 
pressure in the supply air or extract air duct. 

3.2 Supply

An integrated operating switch is located at  
the operating side of the ComfoAir XL unit.  
The connection terminals and connection board are 
located behind the designer front panel. The board is 
equipped with a display as standard, which can be 
used easily to set the desired operating point.  
The power supply is connected to the operating 
switch. All versions, except for ComfoAir XL 6000, 
are equipped with a 230 V/50 Hz/1~ power supply.  
ComfoAir XL 6000 must be equipped with a  
400 V/50 Hz/3~ power supply.

Summary of Contents for ComfoAir XL Series

Page 1: ...Cooling Filtering Heating Ventilation Technical documentation ComfoAir XL 800 6000 The latest generation of ventilation units with heat recovery...

Page 2: ...d be delighted to support you Detailed recommendations based on a special operating point with price details Support in the project draft and implementation Instructions on ventilation systems Telepho...

Page 3: ...s 8 2 9 Design 9 3 Control unit 10 3 1 Controller 10 3 2 Supply 10 4 Quick selection 11 4 1 Coding 11 4 2 Selection schematic 11 4 3 Selection chart 12 5 Dimensions and weight 14 5 1 Indoor installati...

Page 4: ...fic fan output is less than 0 34 W m h 1 3 ComfoAir XL series and options The ComfoAir XL series is available in a variety of versions and with numerous options The focus was placed on the smallest po...

Page 5: ...5 1 4 Block diagram Filter Heater Cooler Heat exchanger Fan Temperature sensor Bypass Flap ODA Outside air EHA Exhaust air ETA Extract air SUP Supply air...

Page 6: ...han 3 An overview of the specifications is provided below Feature Class Mechanical strength 2A Internal leak at 400 Pa 3 of the nominal volume External leak at 400 Pa 3 of the nominal volume Thermal i...

Page 7: ...condensate that forms on the cooler The siphon can be kept frost free by using an insulated ribbon heating element The contact for supply and control can be set in the software 2 5 Bypass ComfoAir XL...

Page 8: ...heat exchanger and can be used as a frost protection system The preheater is calculated on the basis of the water glycol medium to prevent the battery from freezing Post heater The post heater increas...

Page 9: ...Metal support frame ComfoAir XL is equipped with the following components as standard for mounting outdoors G Support frame made of galvanised metal H Coated metallic cover I Two droplet catchers Opt...

Page 10: ...elay Generation of summer night cooling via digital input Compatible with fire alarm system via digital input Summer night cooling activation via an external signal Frost protection for the high perfo...

Page 11: ...r BF Bag filter I Indoor installation O Outdoor installation B Bypass open closed BM Bypass modulating R Right handed version L Left handed version CFE Counterflow plate heat exchanger Product type de...

Page 12: ...ng to NEN 5138 2004 COLD RECOVERY Outside air conditions C RH Extract air conditions C RH Temperature efficiency perceptible performance PREHEATER Air volume m s Air volume m h Temperature distributio...

Page 13: ...1 79 8 79 6 79 8 79 6 28 60 28 60 28 60 28 60 28 60 28 60 24 55 24 55 24 55 24 55 24 55 24 55 79 3 79 6 79 2 79 2 78 9 79 2 0 22 0 42 0 56 0 92 1 22 1 67 800 1500 2200 3300 4400 6000 60 40 60 40 60 40...

Page 14: ...68 875 x 395 310 340 ComfoAir XL 2200 2514 700 1500 612 x 612 450 600 ComfoAir XL 3300 2514 1050 1500 962 x 612 600 750 ComfoAir XL 4400 2514 1400 1500 1312 x 612 750 900 ComfoAir XL 6000 2514 1750 15...

Page 15: ...ComfoAir XL 2200 2514 700 1500 612 x 612 560 750 ComfoAir XL 3300 2514 1050 1500 962 x 612 730 920 ComfoAir XL 4400 2514 1400 1500 1312 x 612 900 1090 ComfoAir XL 6000 2514 1750 1500 1662 x 612 1070...

Page 16: ...6 6 Technical data 6 1 Technical data ComfoAir XL 800 Specific fan power pressure loss and sound level Supply air max line Extract air max line Cooler supply air pre heater and post heater Sound level...

Page 17: ...m3 h P Pa 125 Hz dB 250 Hz dB 500 Hz dB 1000 Hz dB 2000 Hz dB 4000 Hz dB LwA dB A 1 363 52 56 8 46 2 37 5 38 0 31 8 22 4 45 2 625 150 60 6 52 4 43 0 42 6 36 1 27 8 49 3 818 260 64 9 59 3 49 2 47 9 40...

Page 18: ...18 6 2 Technical data ComfoAir XL 1500 Specific fan power pressure loss and sound level Supply air max line Extract air max line Cooler supply air pre heater and post heater Sound level...

Page 19: ...3 h P Pa 125 Hz dB 250 Hz dB 500 Hz dB 1000 Hz dB 2000 Hz dB 4000 Hz dB LwA dB A 1 881 86 61 0 59 5 55 2 49 6 45 9 37 6 57 2 1119 139 61 8 61 7 57 4 51 5 47 6 39 6 59 3 1528 260 63 7 66 6 62 3 55 8 51...

Page 20: ...20 6 3 Technical data ComfoAir XL 2200 Specific fan power pressure loss and sound level Supply air max line Extract air max line Cooler supply air pre heater and post heater Sound level...

Page 21: ...3 h P Pa 125 Hz dB 250 Hz dB 500 Hz dB 1000 Hz dB 2000 Hz dB 4000 Hz dB LwA dB A 1 986 50 60 1 63 6 49 5 49 3 41 4 33 8 57 2 1498 116 65 3 66 0 59 7 58 0 49 4 42 2 63 3 2187 247 72 4 69 3 73 4 69 6 60...

Page 22: ...22 6 4 Technical data ComfoAir XL 3300 Specific fan power pressure loss and sound level Supply air max line Extract air max line Cooler supply air pre heater and post heater Sound level...

Page 23: ...h P Pa 125 Hz dB 250 Hz dB 500 Hz dB 1000 Hz dB 2000 Hz dB 4000 Hz dB LwA dB A 1 1788 73 64 5 64 6 59 3 49 2 46 6 38 3 60 2 2623 158 66 4 72 4 67 4 56 5 53 0 45 4 68 3 3334 255 68 0 79 1 74 4 62 7 58...

Page 24: ...24 6 5 Technical data ComfoAir XL 4400 Specific fan power pressure loss and sound level Supply air max line Extract air max line Cooler supply air pre heater and post heater Sound level...

Page 25: ...h P Pa 125 Hz dB 250 Hz dB 500 Hz dB 1000 Hz dB 2000 Hz dB 4000 Hz dB LwA dB A 1 2228 64 65 4 59 1 53 4 49 9 47 3 37 2 57 2 3261 137 74 2 77 7 67 8 64 8 63 1 55 9 73 3 4453 256 75 3 83 7 72 6 69 9 69...

Page 26: ...26 6 6 Technical data ComfoAir XL 6000 Specific fan power pressure loss and sound level Supply air max line Extract air max line Cooler supply air pre heater and post heater Sound level...

Page 27: ...3 h P Pa 125 Hz dB 250 Hz dB 500 Hz dB 1000 Hz dB 2000 Hz dB 4000 Hz dB LwA dB A 1 3105 67 70 6 72 0 60 4 56 6 52 5 42 2 66 2 4592 146 75 4 78 8 68 2 65 1 61 2 51 9 73 3 5899 242 79 6 85 4 75 1 72 8 6...

Page 28: ...basis of the ventilation requirement in the room If the CO2 concentration is high the ventilation stage is increased automatically If the CO2 concentration is low the ventilation stage is reduced aut...

Page 29: ...bH Sales International Almweg 34 77933 Lahr Germany T 49 7821 586 392 F 49 7821 586 406 sales international zehndergroup com www international zehnder systems com Z_SI_V0414_CSY_DAS_ComfoAirXL en subj...