Setting additional programmes (Optional)
Additional programme values
Submenu description
Minimum
Maximum
Factory reset
P60
Confirming the presence of a geother-
mal exchanger (EWT).
• 0; geothermal heat exchanger not
fitted
• 1; geothermal heat exchanger fitted
• 3; geothermal heat exchanger un-
regulated.
0 (= No)
3 (= Yes)
0
If a valveless geothermal heat exchanger is fitted, then the unregulated
setting must be selected so that the ventilation unit's bypass valve con-
tinues to function properly.
P61
Setting the percentage by which the sup-
ply fan must increase its speed when the
valve of the geothermal heat exchanger
(EWT) is opened.
0%
99%
0%
P62
Tge (= outside air temperature
for the geothermal heat exchanger), low
0%
15%
7%
Note:
The geothermal heat exchanger valve opens if the temperature falls
below the set temperature. The geothermal heat exchanger valve closes if the
temperature rises above the set temperature.
The geothermal heat exchanger valve only responds if the ventilation unit
is in winter mode.
P63
Tge (= outside air temperature for the
geothermal heat exchanger), high
10%
25%
23%
Note:
The geothermal heat exchanger valve opens if the temperature rises
above the set temperature. The geothermal heat exchanger valve closes if the
temperature falls below the set temperature.
The geothermal heat exchanger valve only responds if the ventilation unit
is in summer mode.
P64
Tah (= temperature of the reheater),
required
5%
40%
18%
Note:
The reheater will be deactivated once the set temperature has been
reached.