EN 19
Values of analogue port
Submenu description
Minimum Maximum Factory reset
845
0=positive analogue input 4 1=negative setting
analogue input 4
0
1
0
846
read-out analogue input 4
0
100
-
850
RF input 1
0= not fitted 1 = fitted
0
1
0
851
0= control 1 = programme
(rF input 1)
0
1
0
852
set point rF input 1 (programming)
0
100
50
853
min. setting RF input 1
0
99
0
854
max. setting RF input 1
0
100
100
855
0=positive rF input 1 1=negative setting rF
input 1
0
1
0
856
Read-out RF input
0
100
-
Menu P9
Status of programmes
(from menus P5 and P6: additional programmes)
Status
Sub-menu
description
Activated
P90
Open fire programme active?
Yes (1) / No (0)
P91
Bypass Open (=Yes) / Closed (=No)?
Yes (1) / No (0)
P92
Geothermal heat exchanger valve
Open (=Yes) / closed (=No)
Yes (1) / No (0)
P93
Reheater active?
Yes (1) / No (0)
P94
0 – 10 V programme active?
Yes (1) / No (0)
P95
Frost protection or frost-free element
active?
Yes (1) / No (0)
P96
ComfoHood programme active?
Yes (1) / No (0)
P97
Enthalpy programme active?
Yes (1) / No (0)
5.3 P menus ComfoCool
Temperature values
Submenu description
Minimum Maximum Factory reset
P42
Current value of Condenser
(= temperature of the condenser in the Comfo-
Cool)
-
-
Current ºC
Note: The temperature should never exceed 58°C. At 50°C and above, a cooling-down
programme is activated.
P43
Current value of Supply
(= temperature of the supply air of the ventila-
tion unit)
0
1
0
P71
n/a
0
100
Current ºC