6 - EN
Problem/
malfunction
Indications
Check / action
No cooling
CC displays: “E15”
The heat-recovery unit is not sending a signal to the ComfoControl Luxe. Check
the connection between the ComfoControl Luxe and the heat-recovery unit.
CC displays: “E16”
The ComfoCool is not sending a signal to the heat-recovery unit. Check the
data cable connections between the ComfoCool and the heat-recovery unit.
CC displays: “E2”
The supply valve is deactivated or fails to give a signal. Please refer to the heat-
recovery unit manual for a solution to this problem.
CC displays: “E1”
The exhaust valve is deactivated or fails to give a signal. Please refer to the
heat-recovery unit manual for a solution to this problem.
CC displays:
“NO COOLING”
The ComfoCool cannot be activated. Check the ambient conditions.
Irregular ventilation none
Check whether the ventilation level is high enough. Check that the flow rate is
set-up properly. At least 200m
3
/h is required for effective operation. If the flow
rate is set up too low, then the unit will increase it briefly to keep the condenser
temperature at a safe level.
5.3. Service parts
Part
Article number
ComfoCool Skid
400400040
ComfoCool data cable
400400041
ComfoCool PCB
400300070
NTC supply sensor
400300071
NTC condenser sensor
400300072
Overpressure switch
400300073
Adaptor set ComfoAir 350
471400050
Support frame ComfoAir 350
642300135
Adaptor set ComfoAir 550
471400055
Support frame ComfoAir 550
642300140
ComfoControl Luxe
655010110
5.4. End of useful life
When scraping the unit or the cooling skid, contact your
local authority to enquire what the possibilities are for
recycling or processing. The ComfoCool contains coolant
R134a. It is essential that the coolant is disposed of in an
environmentally friendly manner. If not disposed of prop-
erly, the contribution to greenhouse gas emissions of the
volume of coolant in this system equals 700kg CO
2
.