EN    22   

8.2   Fluid mixture

Desired ethylene glycol percentage

Maximum outdoor temperature [ºC]

Percentage [%]

-15 

35

-20 

40

-25 

45

-30 

50

8.3   Fluid pump settings

Terrestrial heat 

collector 

internal diameter 

[mm]

Terrestrial heat 

collector 

length [m]

Fluid pump setting 

Comfofond-L 350

Fluid pump setting 

Comfofond-L 550

18,0

65

7

(use thicker pipe)

20,4

65-75

5

(use thicker pipe)

20,4

76-90

6

(use thicker pipe)

20,4

91-100

7

(use thicker pipe)

26,2

65-100

4

5

26,2

101-150

5

6

26,2

151-200

6

7

26,2

201-250

7

(use thicker pipe)

29,0

65-100

3

4

29,0

101-175

4

5

29,0

176-250

5

6

29,0

251-300

6

7

29,0

301-400

7

(use thicker pipe)

32,6

65-100

3

4

32,6

101-200

4

5

32,6

201-325

5

6

32,6

326-450

6

7

32,6

451-600

7

(use thicker pipe)

8.4  Air resistance

Higher concentrations of ethylene glycol 
can cause flow-related problems on 
account of the viscosity of the mixture. 
Irreversible damage will be caused to 
the machine if concentrations in excess 
of 50% are used.

Summary of Contents for ComfoFond-L

Page 1: ...Installation manual Installatie handleiding Installation Anleitung Manuel de l installateur Manuale per l installatore Instrukcja obs ugi Comfofond L comfosystems...

Page 2: ...II All rights reserved This documentation has been compiled with the utmost care The publisher cannot be held liable for any damage caused as a result of missing or incorrect information in this manu...

Page 3: ...loop terrestrial heat collector 10 4 5 Electrical connections 11 5 Commissioning 12 5 1 Filling the brine loop 12 5 2 Adjusting the fluid pump 13 5 3 Registering the Comfofond L on the ComfoAir Luxe 1...

Page 4: ...ne loop dimensions 20 8 2 Fluid mixture 21 8 3 Fluid pump settings 21 8 4 Air resistance 21 8 5 Cooling capacity 22 8 6 Heating capacity 22 8 7 Service parts 23 9 CE certification and warranty 24 I In...

Page 5: ...g pictograms are used in this manual Point to watch Risk of damage to the device performance of the unit is compromised if instructions are not observed carefully Risk of personal injury for the user...

Page 6: ...is manual Personal injury or damage to the Comfofond L can arise from non compliance with the safety regulations warnings comments and instructions in this manual The Comfofond L may only be fitted co...

Page 7: ...llation conditions and dimensional sketches In order to determine whether the Comfofond L can be installed in a certain area the following aspects must be taken into account The Comfofond L must be in...

Page 8: ...EN 4 3 1 Dimensional sketch Comfofond L 350 L Elevation P...

Page 9: ...EN 5 3 2 Dimensional sketch Comfofond L 350 R Elevation P...

Page 10: ...EN 6 3 3 Dimensional sketch Comfofond L 550 L Elevation P...

Page 11: ...EN 7 3 4 Dimensional sketch Comfofond L 550 R Elevation P...

Page 12: ...air Comfofond L 550 Comfofond L 550 Left Right 4 2 Wall mounting Mount the Comfofond L against a wall with a minimum mass of 200 kg m2 The Zehnder base frame optional extra must be used for other wal...

Page 13: ...r connections on the Comfofond L and the ComfoAir Luxe vapour proof A A Metal sleeve joint B Plastic sleeve joint 7 Fit the condensation drain to the underneath of the Comfofond L 4 3 Connecting the c...

Page 14: ...actual length for the calculation is the length that is physically in the ground The length inside the house has no further effect on the energy that the system can extract The required pipe length fo...

Page 15: ...fed by the ComfoAir Luxe To do so the temperature sensor and fluid pump of the Comfofond L must be connected to the Luxe connection printed circuit board on the ComfoAir Luxe This Luxe connection pri...

Page 16: ...removing the 6 screws 6 Remove the front panel from the Comfofond L 7 Set the fluid pump to the highest setting by turning the switch on the pump to setting 7 8 Connect a filling hose with external fi...

Page 17: ...l which can be used to note the setting used 5 3 Registering the Comfofond L on the ComfoAir Luxe The control for the Comfofond L is not activated as standard on the ComfoAir Luxe This must be registe...

Page 18: ...3 of the ComfoAir Luxe In the Winter mode the ComfoAir Luxe will switch around the temperature that is set in P menu P62 The best setting for P menu P62 is a few degrees below the lowest fluid tempera...

Page 19: ...perature 8 Press OK MENU P60 will be displayed on the screen 9 Press OK MENU 2 times Current ventilation setting will be displayed on the screen Setting temperature via CC Ease 1 Press and together fo...

Page 20: ...To ensure a hassle free lifespan for your Comfofond L we recommend you take out a service agreement with an expert company The following maintenance may be carried out by the user Replacing the filte...

Page 21: ...ure is 1 5 bar Filling instructions Only a recognized cooling technology fitter may top up the Comfofond L Top up the system as follows 1 Disconnect the ComfoAir Luxe from its power supply 2 Remove th...

Page 22: ...valve V3 slowly until the system is depressurised 5 Replace the fluid pump 6 Top up the system to the nominal pressure of 1 5 bar in accordance with the filling instructions in the brine loop maintena...

Page 23: ...h the power supply to the ComfoAir Luxe back on as described in the maintenance section for the brine loop 6 11 Replacing de aerator 1 Remove the front panel of the Comfofond L as described in the bri...

Page 24: ...nect the siphon Condensation leak Condensation drain clogged Clean both condensation drains at the top and bottom of the Comfofond L Condensation on the pipes and or fluid and air connections Insulate...

Page 25: ...1800 W 2500 W Cooling capacity 2000 W 3000 W Maximum sound capacity 40 dB A 40 dB A Ideal fluid pressure 1 5 bar 1 5 bar Fluid volume Comfofond L 2 l 2 l Fluid flow rate 6 8 l min 8 10 l min Fluid com...

Page 26: ...76 90 6 use thicker pipe 20 4 91 100 7 use thicker pipe 26 2 65 100 4 5 26 2 101 150 5 6 26 2 151 200 6 7 26 2 201 250 7 use thicker pipe 29 0 65 100 3 4 29 0 101 175 4 5 29 0 176 250 5 6 29 0 251 300...

Page 27: ...uid 6 l min T air in 35 C RH 50 Comfofond L 550 Qv fluid 8 l min T air in 35 C RH 50 T air out C T air out C T air out C T air out C 8 6 Heating capacity Comfofond L 350 Qv fluid 6 l min T air in 12 C...

Page 28: ...icle number 1 Filter set G4 G4 006040202 1 Filter set F7 G4 006040250 1 Filter set F7 F7 006040212 1 Individual filter G4 006040200 1 Individual filter F7 006040210 2 Fluid pump Left 2 Fluid pump Righ...

Page 29: ...plied by the manufacturer Unauthorized alterations and or modifications have been made to the unit Liability The Comfofond L has been designed and manufactured for use in balanced ventilation systems...

Page 30: ...led by Address Town city Residence Comfofond L type 350 550 Left Right Settings ComfoAir Luxe P menu P62 Delete as applicable P menu P63 Terrestrial heat collector details Fluid volume Selected glycol...

Page 31: ...EN 27 II Maintenance log Date Activity Initials...

Page 32: ...O Tel 39 0 59 9786200 Fax 39 0 59 9786201 Internet www comfosystems it E mail info comfosystems it Nederland The Netherlands Zehnder Group Nederland B V Lingenstraat 2 8028 PM Zwolle Tel 0900 555 1937...

Reviews: