7.3. Control terminals and user connections
Control board terminal blocks
Abbreviation
Definition
Terminals
Connection
ADP
Fire service remote stop
21-22
To be connected to the terminals of an NC contact of the fire
service remote stop.
(Shunt between terminals 21 -22 on release from factory)
THA
Anti-freeze thermostat
24-28
To be connected to the NC contact of the anti-freeze
protection thermostat THA
(PREMIUM BC and INFINITE BC versions of units equipped
with a hot coil)
HRT
Safety thermostat
24-28
To be connected to the NC contact of the safety thermostat
THS
(PREMIUM BE and INFINITE BE versions units equipped with
an electric heating coil)
MF PV
Low-speed forced
operation
DI3 controller
+ 73
To be connected to an external NO dry contact (normally
open)
MF GV
Low-speed forced
operation
DI4 controller
+ 74
To be connected to an external NO dry contact (normally
open)
ARR EXT
External stop
DI5 controller
+ 75
To be connected to an external NO dry contact (normally
open)
V3V BC
3-way valve Hot water
heating coil
AO1 controller
+ 76 + 78
To be connected to the modulating 3-way valve of the hot
water coil (see XIX CUSTOMER CONNECTIONS WIRING
DIAGRAM)
AL
Alarm reporting
DO5 controller
+ 47
24 V output available if the unit is faulty
(Note 24 Vac output to be relayed)