49
Zehnder Eversky
17. CO₂ concentration sensor
The CO₂ sensor is sited in the air extraction circuit (see chapter VII.1 General composition) and must not be moved. It
informs the controller of the CO₂ concentration in the room,which then adjusts the fan speed accordingly.
The CO₂ sensor transmits the image of the CO₂ concentration (ppm) contained in the extracted air in the form of an
analogue 0-10 V signal that can be interpreted by the controller:
Ambient air naturally contains a variable amount of CO₂ depending on the location. This concentration is generally
above 300 ppm for a non-urban location and can exceed 700 ppm for a very dense urban location.
The output signal of the CO₂ sensor is therefore never zero and should normally always be greater than 3 V. If this is not
the case, there may be a problem with the sensor or the connection.
EVERSKY
™
MS-CDF-019 - N° DE FAB : 220001→
Indice A Mise à jour : 02/05/2022
45/71
L’air ambiant contient naturellement une part de CO2 variable selon l’endroit où l’on se situe. Cette concentration se situe
généralement toujours au-dessus de 300ppm pour une localisation extra urbaine et peut dépasser 700ppm pour une localisation
urbaine très dense.
Le signal de sortie de la sonde de CO2 n’est donc jamais nul est doit normalement être toujours supérieur à 3V. Dans le cas, inverse
il est possible que la sonde ou la connectique présente un problème.
Représentation visuelle de la sonde de CO2 et des bornes de raccordement électrique
L’alimentation 24Vac se fait entre les bornes (7) et (8) et le signal analogique 0-10V de sortie se situe sur la borne (2).
CO
2
2
7 8
V
0...
10 V
24 V
AC
GO G
- +
The 24 Vac supply is between terminals (7) and (8) and the 0-10 V analogue output signal is on terminal (2).
Visual representation of the CO₂ sensor and the electrical connection terminals
Output signal (V)
10
0
0
300
700
2000
CO₂ concentration (ppm) in air