Table A1: Vertical AHRI approved standard ratings
4
Ratings
Unit size
02
03
04
06
08
10
12
Certified
cooling ratings
(3 row main coil)
Total MBH
5.5
7.2
12.0
15.1
19.9
25.7
31.6
Sensible MBH
4.0
4.9
8.9
10.9
14.4
20.1
24.6
GPM
1.1
1.4
2.3
3.0
4.3
5.2
6.4
PD, ft. of H
2
O
2.8
4.9
14.4
5.2
11.0
8.1
12.8
Heating capacity
(3 row main coil)
MBH
18.7
24.5
42.3
56.6
73.4
88.8
99.9
GPM
2.0
2.6
4.7
6.7
8.9
10.2
11.3
PD, ft. of H
2
O
9.3
16.6
11.9
26.3
21.2
19.0
24.4
Certified
cooling ratings
(4 row main coil)
Total MBH
6.4
8.4
13.3
18.7
24.4
28.2
32.8
Sensible MBH
4.1
5.6
9.6
13.8
18.6
20.6
25.0
GPM
1.3
1.7
2.5
3.6
4.8
5.7
6.6
PD, ft. of H
2
O
4.6
9.9
4.4
10.0
7.7
7.1
9.9
Heating capacity
(4 row main coil)
MBH
19.9
25.5
46.3
65.8
87.0
99.2
110.9
GPM
1.9
2.5
4.3
5.8
7.5
9.1
10.2
PD, ft. of H
2
O
6.2
11.8
35.8
15.2
26.1
20.2
26.7
Heating capacity
(optional 1 row
reheat coil)
MBH
7.4
10.5
16.9
25.1
31.8
37.3
43.2
GPM
0.8
1.1
1.7
2.6
3.2
3.8
4.4
PD, ft. of H
2
O
0.1
0.2
0.5
1.1
1.8
2.6
3.5
CFM: standard
High
180
230
440
625
860
1000
1190
Medium
145
160
325
360
650
675
900
Low
115
130
235
250
335
475
500
CFM: high static
(@ 0.2" ESP)
High
350
400
570
660
1000
1160
1210
Medium
320
370
530
600
910
1100
1130
Low
280
330
430
520
780
950
970
Coil
FPI
12
12
12
12
12
12
12
Face area, ft
2
0.94
1.25
1.56
2.19
2.50
2.92
3.44
Coil connections
1/2" Cu
1/2" Cu
1/2" Cu
1/2" Cu
1/2" Cu
1/2" Cu
1/2" Cu
Blower
Quantity
1
1
2
2
1, 2
4
4
Diameter
5.7"
5.7"
5.7"
5.7"
5.7"
5.7"
5.7"
Width
7.5"
10.4"
7.5"
10.4"
7.5", 10.4"
7.5"
10.4"
Filter
Number
1
1
1
1
1
1
1
Length, in.
22
28
34
46
52
60
70
Width, in.
9.75
9.75
9.75
9.75
9.75
9.75
9.75
Thickness, in.
1
1
1
1
1
1
1
Cabinet size
Height, in.
26.5
26.5
26.5
26.5
26.5
26.5
26.5
Length, in.
38.2
44.2
50.2
62.2
68.2
76.2
86.2
Width, in.
10
10
10
10
10
10
10
Minimum free area
Inlet, in
2
99
126
153
207
234
270
315
Outlet, in
2
92
110
129
184
220
257
294
Shipping weight, lbs.
90
105
120
145
160
175
200
Notes:
Airflow under dry conditions. Inlet air 70-80 °F DB
Cooling capacity based on inlet air 80 °F DB, 67 °F WB, 45 °F
entering water, 55 °F leaving water, high fan speed
Heating capacity based on inlet air 60 °F DB, 180 °F entering water,
160 °F leaving water, high fan speed
Pressure drop (PD) shown in feet of water
Overall length for fully and partially recessed units is ( 3").
Wall rough-in hole dimension to be ( 1/8") by 24-1/8" width.
Height dimension applies to floor units only. Wall units are 24".
Sloped top units are 29-1/4".
All units supplied with replaceable filter.
Model FF and FS filters are 7.25" width.
Model FFH 4 row total MBH should be multiplied by 0.93.