6
3.1.1 KEYS FUNCTION
TEST:
When
pushed for 3 sec. during normal operation, it activates the condensate drain.
If pushed while the display shows Energy saving values, resets the counter.
SET:
When pushed and released during normal operation, it displays the dew point set value (decimal).
When pushed for 10 seconds, it allows to enter the C8 and C9 condensate drain parameters programming menu (see
relevant table).
When pushed after having set new configuration values, it stores the applied modifications.
DOWN:
When pushed while setting the drain set point, it decreases the displayed value of one unit per second, during the
first 10 seconds, then one unit every 0.1 sec.
When pushed for 10 seconds during normal operation, it starts an automatic test cycle of the controller.
UP:
When pushed while setting the drain set point, it increases the displayed value of one unit per second, during the first
10 seconds, then one unit every 0.1 sec.
ON / OFF:
Pushed, it activates or deactivates the dryer. When the dryer is deactivated, the display shows OFF.
SET+DOWN:
When pushed simultaneously for 1 second, the dislay shows in sequence the the Energy Saving value of the
last cycle (iSt) and the value of the last 100 hours (tot). The Energy Saving value is the percentage of time in which the
dryer is in ESA/ES2 mode.
NOTE: when the controller is in the OFF position, some parts of the dryer may still be energized. Therefore, for
safety purposes, disconnect the electrical power before performing any maintenance operation on the dryer.
3.1.2 CONDENSATE DISCHARGE PARAMETERS PROGRAMMING
Push the SET key for 10 seconds to enter the parameters configuration menu: the display will show in
sequence the set point value, the code of the first modifiable parameter (C8) and its value).
Only if strictly necessary, use the UP and/or DOWN keys to change the displayed parameter value.
Press the SET key to store the previously changed parameter value or to browse the parameters without
changing them.
15 seconds after the last performed operation, the controller will return automatically to the normal
operation mode.
PARAMETER
DESCRIPTION
RANGE
DEFAULT SET VALUE
C8
Delay between condensate
discharges
1 - 999 (min)
1
C9
Time required for condensate
discharge
1 - 999 (sec)
1
NOTE: Changes entered for timing values will be effective only after exiting the programming, while changes to other
variables will be immediately effective.
Please remember that changes to the configuration parameters of the machine could negatively affect its efficiency. Thus,
changes must be performed by a person familiar with the operation of the dryer.
WARNING FOR USER:
IT’S FORBIDDEN TO ATTEMPT TO MODIFY THE OTHER CONFIGURATION PARAMETERS OF THE ELECTRONIC
CONTROLLER WITHOUT AUTHORIZATION AND COLLABORATION WITH AN AUTHORIZED ZEKS DISTRIBUTOR.