I0055 RevB
Page 21
SS6000 Networking Guide
Output Setting
Encoding
Description
Y10 Relay 1 Mode
Y20 Relay 2 Mode
Y30 Relay 3 Mode
Y40 Relay 4 Mode
0: Disabled
1: Enabled
2: Inverted
Set to enable relay output (RL1…4). The
polarity can be set to suit application.
Y11 Relay 1 Variable
Y21 Relay 2 Variable
Y31 Relay 3 Variable
Y41 Relay 4 Variable
0: Test (On)
1: Fan Control
2: Line Control
3: Bypass Control
4: Acceleration Ramp
5: Deceleration Ramp
6: Ramping
7: Up To Speed
8: Motor On
9: Trip Alarm
10: Motor Loss
11: Frequency Error
12: Bypass Fault
13: Stater OL Trip
14: Motor OL Trip
15: Motor OT Trip
16: Phase Rotation
17: Digital Input Trip
18: Over Time
19: Voltage Imbalance
20: Current Imbalance
21: Under Current
22: Over Current
23: Under Torque
24: Over Torque
25: Warning Alarm
26: TOL Warning
27: Regen Power
28: AR Pending
29: AR Lockout
30: ESO Proof
31: Timer Relay
32: Brake Fault
Sets the function of relay outputs (RL1…4).
Polarity is also configurable
Y50 Analogue Output Mode 0: Disable
1: 0-5V
2: 0-10V
3: 0-20mA
4: 4-20mA
Set electrical characteristics of the analogue
output
Y51 Analog Output Variable 0: Test (100%)
1: Motor Current (def)
2: Motor Torque
3: Motor Thermal
4: Stater Thermal
5: Active Power
6: Power Factor
Select variable for the analogue output. Use
Test (100%) to check analogue output is
working.