background image

Page 6 of 12 

Zenith Autoboil - Installation & Operating Instructions - 81433 - June 2012 v1.01

Step 3 – Connecting

a) Plumbing

For exposed plumbing connection, connect the cold water inlet pipe from the base 
of the heater directly to the 1/2” or 12.7 mm compression fittings.

For concealed plumbing connections, connect the cold water pipe through the rear 
of the chassis using a 1/2” or 12.7 mm capillary elbow (# 63 Swivel Elbows).

Cold water pipes must be flushed before connection to the inlet. Any clogging 
due to sediment or fines will adversely affect the operation of the heater.

It is recommended that the heater be installed with a stop cock which allows it 
to be isolated from the mains supply for servicing.

Water pressure requirements:

Minimum - 1 bar (100 kPa)  maximum - 7 bar (1000 kPa).

Warning:

 If pressure is likely to exceed 7 bar, a pressure limiting valve must be 

installed in the cold water supply line. Zenith recommends a valve rated at 3.5 
bar (350 kPa) for this application.

b) Venting

A vent at the base of the heater must be plumbed to a safe visible location as, 
under certain conditions, it may discharge cold or boiling water and/or steam.

For exposed vent plumbing, connect vent outlet from the base of heater to a 1/2” 
or 12.7 mm pipe which has a continuous fall, is no more than 3 meters long, has 
no more than 3 right angle bends, and discharges to a waste water drain.

For concealed vent plumbing, connect plumbing to the vent outlet from the 
heater rear using a capillary elbow protruding 45 mm from the wall.

Alternatively attach a tun dish to the wall as shown and plumb away to waste.

d) Electrical

For concealed electrical connection, connect a power cable through the rear 
access opening of the heater to the terminal block within the heater as shown.

For exposed electrical connection, connect a flex to a standard 13 amp double 
pole fused spur power outlet on the wall within 1500 mm of the heater.

All isolation switches must have a contact separation of at least 3 mm in all poles.

Do not turn the power ON until the heater is filled with water.

Step 4 – Assembling

Place the heater case back on to the heater and secure the top 2 case screws. 
Secure two bottom case screws.

Step 5 – Commissioning 

Check previous steps. Turn water supply ON. Water is now flowing into heater, 
check connections for leaks. Wait approximately 5 minutes and check outlet 
tap for water. This is achieved by pulling the tap handle forward. 

Power is only to be turned on when water is available from this outlet.

Turn power ON. After a short period, boiling water will be available and will be 
maintained close to boiling point thereafter. Initial heating periods are shown in 
the table on the left.  

Installation Procedures 

Continued

250mm

Wring

Concealed

Vent

Concealed

Inlet

45 mm

Visible Tundish

Vent line

Inlet water 
temperature

15°C

10°C

1.5 Litre models

10 min 11 min

3.0 Litre models

16 min 17 min

5.0 Litre models

16 min 17 min

7.5 Litre models

23 min 24 min

Summary of Contents for Autoboil 01652

Page 1: ...Instructions 81433 June 2012 v1 01 Page1 of 12 Installation and Operating Instructions Autoboil Instant boiling water 01652 Autoboil 1 5 Litre White 03652 Autoboil 3 0 Litre White 05652 Autoboil 5 0...

Page 2: ...Page 2 of 12 Zenith Autoboil Installation Operating Instructions 81433 June 2012 v1 01 Intentionally left blank...

Page 3: ...5 Step 2 Fastening 5 Step 3 Connecting 6 a Plumbing 6 b Venting 6 c Electrical 6 Step 4 Assembling 6 Step 5 Commissioning 6 Wall Mounting Template Dimensions Electrical Diagram 7 Problem Solving 8 Ea...

Page 4: ...t use strong corrosive or abrasive cleaners to clean the case of the heater Frost protection If this heater is located where ambient air temperature could fall below 5 C when the heater is not in use...

Page 5: ...aining board or drip tray Position the base of the tap to be not less than 200 mm above the draining board height should be increased only if essential for filling larger vessels Provide clearance for...

Page 6: ...or concealed vent plumbing connect plumbing to the vent outlet from the heater rear using a capillary elbow protruding 45 mm from the wall Alternatively attach a tun dish to the wall as shown and plum...

Page 7: ...ing Template Dimensions Electrical Diagram 1 5L 3 0 L 5 0 L 7 5 L 65 CLEAR 56 COLD INLET 72 15 25 35 42 POSITIONING PIN VENT EXTERNAL PLUMBING ELECTRICAL WIRING POSITION INTERNAL PLUMBING BENCH TOP 31...

Page 8: ...th authorised agent Warning this appliance must be earthed Following remedial service the earthing continuity of the heater must be checked by a qualified technician using an appliance tester or conti...

Page 9: ...ing water will flow until the tap handle is released This operation gives fingertip flow control for safe filling of cups and mugs To fill larger vessels such as teapots and saucepan s rotate the tap...

Page 10: ...rload kit Autoboil 2000B 14 90501NZ Tap Top Kit Autoboil 2000B 15 90562NZ Tap Assy complete 2000B 16 90503NZ Strap and key kit 1 5 3L 2000B 16 90504NZ Strap and key kit 5 7 5L 2000B 17 90505NZ Tap nut...

Page 11: ...Zenith Autoboil Installation and Operating Instructions 81433 June 2012 v1 01 Page11 of 12 Spare Parts...

Page 12: ...tallation should it become necessary to service the appliance under the terms of Zenith Heaters Limited warranty To register your installation go to www zenithheaters co nz and look under the heading...

Reviews: