Trouble-shooting & Common Questions (cont’d)
15. Replaced Feedback Sensor Fits the Existing ZeDrive Or Not:
16. Display Shows “- - - 1”, “- - - 2”or “- - - 3”:
•
If the AC power setting of ZeDrive sets to 230 VAC ( refer to 12 of this section), it may indi-
cate that the actual AC power is 120 VAC
•
It may also indicate an environment problem, such as electrical noise severe enough to dis-
rupt the microprocessor. Generally,
“- - - 1” indicates incompatible AC power
“- - - 2” indicates electrical noise problem
“- - - 3” indicates parameter storage area has been corrupted
•
If “- - - 2” or “- - - 3” appears, the programming control parameters should be verified and
restoration back to factory settings may be performed (refer to 16 of this section)
17. Restore Back to Factory Defaults:
•
Make sure copy down the original settings, especially the values for the following codes:
Feedback jumper settings on “Control Board” should
match the sensor you have on hand. Check and change
the jumper settings on the “Control Board”:
1. Loosen up 6 screws on the back panel, and 2
screws located on the heat sink of ZeDrive
2. Remove the back panel. Face the back of Ze-
Drive and place ZeDrive so that the heat sink
points down
3. When you place ZeDrive as shown in step 2,
the top board is the “Control Board”, and the
bottom one is “Drive Board”
4. Locate Feedback Jumper as shown at left
5. Check the feedback jumper settings as shown
at the left
Analog I/O Board
(Not this jumper)
Heat Sink
Transformer
Jumper 1
(Feedback)
Feedback Jumper Location
3-wire Sensor (default):
Left
2-wire Sensor:
Left
Code 1 - Primary Setpoint 1
Code 8 - Feedback Input Select
Code 10 - Minimum Limit
Code 11 - Maximum Limit
Code 12 - Low Alarm
Code 13 - High Alarm
Code 16 - Acceleration Time
Code 17 - Deceleration Time
Code 20 - Maximum Primary Setpoint
Code 21 - Maximum Secondary Setpoint
Code 22 - Maximum Primary Display
Code 23 - Maximum Secondary Display
Code 31 - No. of Teeth of the Feedback Pickup Gear
Code 34 - Maximum Motor Speed (Primary)
Code 37 - Maximum Motor Speed (Secondary)
Code 61 - Primary Active Output Format Selection
Code 62 - Secondary Active Output Format Selection
Code 63 - Primary Active Display Format Selection
Code 64 - Secondary Active Display Format Selection
Code 84 - Analog Input Function Selection
Code 85 - Analog Input Zero
Summary of Contents for ZeDrive
Page 10: ...Page 9 TO GET ASSISTANCE CALL 919 774 7667 ZENITH PUMPS Control Cabinet Wiring...
Page 18: ...Page 17 TO GET ASSISTANCE CALL 919 774 7667 ZENITH PUMPS Typical Applications Solutions...
Page 38: ...Page 37 TO GET ASSISTANCE CALL 919 774 7667 ZENITH PUMPS Trouble shooting Fault Information...
Page 45: ...Page 44 TO GET ASSISTANCE CALL 919 774 7667 ZENITH PUMPS Complete Code List...
Page 59: ...Page 58 TO GET ASSISTANCE CALL 919 774 7667 ZENITH PUMPS System Drawings...