DALIBOX Interface 64/32
Technical Support:
12
Sequences
:
up to 16 different sequences, which can be associated to different
groups. Up to five step actions per sequence can be defined, as well as the
dimming type of each step action among other things.
Lock
: group control enabling/disabling, with the additional option to define
actions for the lock and unlock events.
Initialisation
: custom configuration of the initial status (upon the recovery of
the KNX bus power or after an ETS download or a restart) for each group, or
either of an initial sending (immediate or delayed) of the status to the bus
.
Error identification
: detection of anomalies that may affect the proper
operation of the device: power supply error, short circuit, ballast presence error
or ballast and group diagnostic errors.
Special operation modes
:
➢
Auto Off
: mode that allows automatically switching off a group in case it
remains steady under a certain parameterisable dimming threshold for more
than a defined time period.
➢
Burn-in
: mode that prevents the execution of dimming orders during a
certain, parameterisable time period after the switch-on of the ballast, with
the aim of stabilising the lamp response and of optimising its life time. This
feature may be required by certain lamp models.
ECG Automatic Detection
: possibility of enabling the ECG Automatic
Detection.
Collisions Detections
: possibility of enabling the Collisions Detections.
Other than these functions, the general settings of the device allow enabling each of the
64 ballasts (or ECGs)
supported as maximum and assigning it, if desired, any of the
32
groups
available.