DALIBOX Interface 64/32
Technical Support:
34
ETS PARAMETERISATION
As new groups are enabled (see section 2.3), additional sub-tabs will be incorporated
with name “Group N”, being N their specific numbers. These tabs, on their side, contain
a set of new sub-tabs. The first one,
“
Configuration
”, provides the following parameters:
Name
: desired identifier for the group (up to twelve characters).
Diming Value During DALI Bus Failure
[
Off / Defined Vale /
No Change
]: in
case of selecting
“Defined Value” the ballast will switch to a customisable value
[
0
…
100
] [
%
].
Figure 13.
Group 'N'. Configuration
Functions
: checkboxes to enable additional functions for the group:
➢
Status Objects
[
enabled/
disabled
]. See section 2.5.5.
➢
Custom On/Off
[
enabled/
disabled
]. See section 2.5.6.
➢
Timers
[
enabled/
disabled
]. See section 2.5.7.
➢
Lock
[
enabled/
disabled
]. See section 2.5.8.
➢
Custom Initialisation
[
enabled/
disabled
]. See section 2.5.9.
➢
Modes
[
enabled/
disabled
]. See section 2.5.10.
Regulation
[
Logarithmic
/ Linear
]: sets the ballast regulation type.