Each scene activated from this screen will have a specific tab associated, labelled as
“
Scene
‘n’
”, as detailed next.
2.6.2
SCENE N
Each of up to 32 scenes must be assigned a certain identifier, i.e., their scene number
with regards to the KNX system. When this value is received through the scenes object,
the scene will be executed (or saved, in case the value is received incremented by 128,
according to the KNX standard).
The specific action to be performed by each group on the execution of the scene can be
selectively configured.
ETS PARAMETERISATION
Figure 27.
Scene N
Scene Number
[
1…64
]: sets the scene identifying number whose reception
through the “
Scene Control
” object will make the device execute or save the
scene depending on the case.
Associate Group M with This Scene
: allows associating the scene to the
different available groups and configuring the target dimming level (
Value
[
0…
100
] [
%
]) for each one, which can be different. It is important to take into
account that there can be different scenes associated to the same group.