DALIBOX Interface 64/32
Technical Support:
41
2.5.6
CUSTOM ON/OFF
This function offers one additional On/Off control for each group, and therefore another
new communication object to switch the ballasts on and off.
This additional control can be customised with specific dimming levels for the “On” and
“Off” states and may also be configured to perform an immediate or soft dimming.
ETS PARAMETERISATION
Once the function has been enabled, the
“[Group n] Custom On/Off”
one-bit object
and a specific parameter tab will show in ETS:
Figure 18.
Custom On/Off
This new screen allows setting up the specific behaviour when a “1” or a “0” are received
through the aforementioned object:
Dimming Value for Bit Value ‘1’
[
0…
100
] [
%
]: sets a specific dimming
percentage to be applied to the gr
oup when a “1” is received.
Dimming Time for Bit Value ‘1’
[
At Once
/ Dimming Time 1 / Dimming Time
2 / Dimming Time 3
].
Dimming Value for Bit Value ‘0’
and
Dimming Time for Bit Value ‘0’
:
analogous to the above two parameters, but referred to the arrival of the value
“0” from the bus.