DALIBOX Broadcast 6CH/4CH
http://www.zennio.com
Soporte técnico:
http://support.zennio.com
23
Figure 8.
Channel “x”. Error Objects
DALI Error
: enables the “
[Cx] Error: DALI Bus Failure
”
object, which will be
sent periodically with value “1” in case of detecting communication errors or a
short circuit in the DALI bus of the channel. After the error is over, it will be
sent (once) with value “0”.
Ballast Error
: enables the “
[Cx] Error: Ballast Failure
”
object, which will be
sent periodically with value “1” in case of detecting a ballast failure in at least
one of the ballasts connected to the channel. After the error is over, it will be
sent (once) with value “0”.
Lamp Error
: enables the “
[Cx] Error: Lamp Failure
”
object, which will be
sent periodically with value “1” in case of detecting a lamp failure in at least
one of the ballasts connected to the channel. After the error is over, it will be
sent (once) with value “0”.
Ballast Overload Error
: enables the “
[Cx] Error: Ballast Overload
”
object,
which will be sent periodically with value “1” in case of detecting excessive
ballasts connected to the channel. After the error is over, it will be sent (once)
with value “0”.
Open Circuit Error
: enables the “
[Cx] Error: Open Circuit
”
object, which will
be sent periodically with value “1” in case of detecting a short circuit or a
complete absence of ballasts in the channel. After the error is over, it will be
sent (once) with value “0”.
2.2.6
STATUS OBJECTS
DALIBOX Broadcast 6CH / 4CH provides different objects that report the current
dimming state of the output channel: