The
simple timer
function consists in a switch-on of the channel (with an
optional delay) on the reception of the corresponding trigger object, and a
later switch-off, either automatic (after a certain period) or triggered through
the corresponding bus object, also with an optional delay in this case.
On the other hand, the
flashing
function consists in switching the channel on
and off a certain number of times or indefinitely, according to the parameters,
once the corresponding object is received.
ETS PARAMETERISATION
After enabling this option, the following parameters will show in ETS:
Figure 12.
Channel “x”. Timers
Simple Timer
and
Flashing
are disabled by default. Once enabled, the “
[Cx] Simple
Timer
” and “
[Cx] Flashing
” one-bit objects are added to the project topology. An
additional parameter tab for each option shows up too.
Simple Timer
Figure 13.
Simple Timer