DALIBOX Broadcast 6CH/4CH
http://www.zennio.com
Soporte técnico:
http://support.zennio.com
37
ballast overload or open circuit errors will no longer be detected in that
channel.
During
ballast initialisation
or DALI address assignment, any attempts to
activate the Standby mode will be postponed by 30 seconds, as many times
as necessary until such process is finished.
The following example illustrates how the Standby mode works:
Figure 21.
Standby mode action sequence
2.2.12.2
BURN-IN MODE
The Burn-in mode is intended for certain lamp types such (as steam lamps) which need
to remain on for a certain time period
before performing
any light dimming
. Before
the channel has been (steadily) switched on for at least the configured time, it will only
be possible to
switch the loads off or to regulate them to 100%.
In case of having configured any
limits
(either luminosity limits or dimming limits; see
section 2.2.2), they will not be considered while the Burn-in mode is in operation, i.e.,
the loads will be actually switched on entirely. However, they will be applied once the
Burn-in mode is over, which will may be perceived as a slight change in the light level.
This functionality entails certain effects over in other functionalities (while the Burn-in
mode remains active, any dimming order greater than 0% will be executed as an
immediate regulation to 100%, or to 0% in other case):
Relative and absolute dimming.
Simple timers and flashing.
Lock/unlock actions.
Status: 50%
Status: 0%
Dimming: 0%
Standby = 1
Dimming: 50%
Error Detect.
X
Error Detect.
√
Standby = 0
Status: 50%