background image

© Zennio Avance y Tecnología S.L. 

Edition 7 

Further information 

www.zennio.com

 

Page 1/2 

 

DALIBOX Broadcast 6CH 

KNX - DALI Broadcast Interface for up to 6 channels 

ZDI-DLB6 

TECHNICAL DOCUMENTATION 

 

FEATURES 

 

Control of up to 20 DALI ballasts per channel in up to 6 channels 
only for logarithmic curve 

 

Ballast replacement allowed with automatic detection 

 

Error detection and monitoring (except multiaddress DALI ballasts) 

 

Burn-in, Stand-by and Auto-off functionality for each channel 

 

Not suitable for emergency lighting control 

 

Optional manual dimming control 

 

External 110-230 VAC 50/60 Hz power supply 

 

Total data saving on KNX bus failure 

 

Integrated KNX BCU (TP1-256) 

 

Dimensions 67 x 90 x 79 mm (4.5 DIN units) 

 

DIN rail mounting according to IEC 60715 TH35, with fixing clamp 

 

DALI Standard compatible 

 

Conformity with the CE, UKCA, RCM directives (marks on the right 
side) 

 

 

 

1. DALI channel output 

2. DALI channel status LED 

3. DALI channel control button 

4. Programming/Test button 

5. Programming/Test LED 

6. External supply LED 

7. External power supply 

8. KNX connector 

9. Fixing clamp 

7

 

6

 

9

 

Figure 1: DALIBOX Broadcast 6CH 

GENERAL SPECIFICATIONS 

CONCEPT 

DESCRIPTION 

Type of device 

Electric operation control device 

KNX supply 

Voltage (typical) 

29 VDC SELV 

Voltage range 

21-31 VDC 

Maximum 
consumption 

Voltage 

mA 

mW 

29 VDC (typical) 

203 

24 VDC¹ 

10 

240 

Connection type 

Typical TP1 bus connector for 0.8 mm Ø rigid cable 

External power supply 

110-230 VAC 50/60 Hz 

Operation temperature 

-5 .. +45 °C 

Storage temperature 

-20 .. +55 °C 

Operation humidity 

5 .. 95% 

Storage humidity 

5 .. 95% 

Complementary characteristics 

Class B 

Protection class 

II 

Operation type 

Continuous operation 

Device action type 

Type 1 

Electrical stress period 

Long 

Degree of protection 

IP20, clean environment 

Installation 

Independent device to be mounted inside electrical panels with DIN rail (IEC 
60715) 

Minimum clearances 

Not required 

Response on KNX bus failure 

Data saving according to parameterization 

Response on KNX bus restart 

Data recovery according to parameterization 

Operation indicator 

The  programming LED indicates programming mode (red) and  test mode 
(green). Each output LED indicates its status (fixed = active output; flashing 
= error in the output). Power supply LED indicates the presence of supply 
voltage (green). 

Weight 

124 g 

PCB CTI index 

175 V 

Housing material 

PC FR V0 halogen free 

¹ Maximum consumption in the worst-case scenario (KNX Fan-In model). 

Programming/Test button: short press to set programming mode. If this button is held while plugging the device into the KNX bus, it enters the safe 
mode. If this button is held for more than 3 seconds, the device enters the test mode. 
 
Programming/Test LED: programming mode indicator (red). When the device enters the safe mode, it blinks (red) every half second. The manual mode 
is indicated by the green color. During the start-up (reset or after KNX bus failure) and if the device is not in safe mode, it emits a red flash. 