© Zennio Avance y Tecnología S.L.
Edition 1
Further information
Page
1
/
4
inBOX DIM
Universal Dimmer for Flush Mounting - 1 Output (250W@230VAC / 200W@110V) / 2 A/D inputs
ZDI-IBD
Technical Documentation
FEATURES
▪
1 channel for R L C loads and for dimmable CFL and LED lamps.
▪
Automatic detection of R L C load type.
▪
Automatic frequency detection.
▪
Dimming pattern selection for CFL and LED lamps.
▪
Optional manual dimming control.
▪
2 inputs configurable as
▪
Binary input.
▪
Temperature probe.
▪
Motion sensor.
▪
10 logical functions.
▪
External 110/230VAC 50/60Hz power supply.
▪
Total data saving on KNX bus failure.
▪
Integrated KNX BCU.
▪
Dimensions Ø50 x 26mm.
▪
Can be mounted within distribution boxes, junction boxes or wall
back boxes.
▪
Conformity with the CE directives (CE-mark on the back side).
Programming/test button
: short press to set programming mode. If this button is held while plugging the device into the KNX bus, it enters the safe
mode.
If this button is held for more than 3 seconds, the device enters the test mode.
Programming/Test LED:
programming mode indicator (red). When the device enters into safe mode, it blinks (red) every half second. The manual
mode is indicated by the green color. During the start-up (reset or after KNX bus failure) and if the device is not in safe mode, it emits a red flash.
1
. Output status LEDs
2
. Programming/Test button
3
. Programming/Test LED
4
. Inputs
5
. External power supply
6
. Output
7
. Output control buttons
8
. KNX connector
Figure 1.
inBOX DIM
GENERAL SPECIFICATIONS
CONCEPT
DESCRIPTION
Type of device
Electric operation control device
KNX
supply
Voltage (typical)
29VDC SELV
Voltage range
21…31VDC
Maximum
consumption
Voltage
mA
mW
29VDC (typical)
8.2
237.8
24VDC
(1)
10
240
Connection type
Typical bus connector TP1 for rigid cable 0.80mm Ø
External power supply
110/230VAC 50/60Hz
Operation temperature
0ºC to +40ºC
Storage temperature
-20ºC to +55ºC
Operation humidity
5 to 95% RH (no condensation)
Storage humidity
5 to 95% RH (no condensation)
Complementary characteristics
Class B
Protection class
II
Operation type
Continuous operation
Device action type
Type 1
Electrical stress period
Long
Degree of protection
IP20, clean environment
Installation
Independent device to be mounted inside distribution boxes, junction boxes or wall
back boxes.
Minimum clearances
Not required
Response on KNX bus failure
Data saving according to parameterization
Response on KNX bus restart
Data recovery according to parameterization
Operation indicator
The programming LED indicates programming mode (red) and test mode (green).
Each output LED indicates its status (fixed = active output; flashing = dimming error)
Weight
43g
PCB CTI index
175V
Housing material
PC FR V0 halogen free
(1)
Maximum consumption in the worst case scenario (KNX Fan-In model)
3
6
8
2
4
1
7
5