20
20
updated instant values, that is, the peak value until the current portion of the current day, of
the current week and of the current month), however in this case this must be configured
under the General screen, with a unique parameterizable period for the three of them.
The associated objects in this case are
“[Cx] Hourly Peak Power”, “[Cx] Daily Peak Power”,
“[Cx] Weekly Peak Power” and “[Cx] Monthly Peak Power”
3.3.3. POWER LIMIT MONITORING
From this screen it is possible to configure several parameters related to the monitoring of
power consumption in relation to upper and lower limits (section 2.3).
Two different sections can be found, one for configuring the parameters of the upper limit
and one for configuring the parameters of the lower one.
For the upper limit:
Initial value:
allows setting (in tens of a watt) the value that, at least in the beginning, the
Energy Saver will assume as the upper limit while measuring power.
If the value “0” is set,
KES will not consider monitoring power in relation to a particular upper limit. The value of the
upper limit, however, can be modified in runtime through the communication object
“[Cx]