ZENN
iO
AVANCE Y TECNOLOGÍA
vwww.zennio.com
40
ANNEX III. COMMUNICATION OBJECTS
SECTION
NUMBER
SIZE
IN/OUT FLAGS
VALUES
NAME
DESCRIPTION
RANGE
1st TIME
RESET
GENERAL OBJECTS
0
3 bytes
I
WT
0:00:00 -
23:59:59
0:00:00
Previous
Time
Current Time
1
3 bytes
I
WT
01/01/1990
–
31/12/2089
01/01/2000
Previous
Date
Current Date
2
1 bit
I
W
0/1
0
0
Global Reset
0=No action; 1=Reset
3
1 bit
I
W
0/1
0
0
Global Request
0=No action; 1=Request
13-16
2 bytes
I
W
0-65535
Depends on
initial paramet.
Previous
Tariff
x [x=1…4]
Tariff value
17-20
1 bit
I
W
0/1
0
0
Switch to tariff
x [x=1…4]
0=No action; 1=Switch Tariff
CHANNELS: GENERAL
OBJECTS
4-6
1 bit
I
W
0/1
0
0
[Cx] Reset
0=No action; 1=Reset
7-9
1 bit
I
W
0/1
0
0
[Cx] Request
0=No action; 1=Request
10-12
1 bit
I
W
0/1
0
Previous
[Cx] Disable
0=Disable; 1=Enable
CHANNELS: ACTIVE
ENERGY OBJECTS
21-23
4 bytes
O
RT
0 - 2
32
0
Previous
[Cx] Estimated energy consumption
Estimated energy consumption
24-26
2 bytes
O
RT
0 - 670760
0
Previous
[Cx] Estimated cost
Estimated cost
27-29
2 bytes
O
RT
0 - 2
32
0
Previous
[Cx] Last hour energy consumption
Last hour energy consumption