KLIC-DD3
http://www.zennio.com
Technical Support:
http://support.zennio.com
23
Vertical Flaps
: “Last (before restart)”, “Swing Off” (flaps without movement)
or “Swing On” (flaps in movement). This option only will be visible in case of
having enabled this kind of flaps; on the contrary this section will appear as
“Not Available”.
Humidifying Unit
: permits selecting a humidity operation point from the
values
: “Last (Before Restart)”, “Off”, “Low”, “Standard”, “High” o
“Continuous”.
Notes
:
This parameter is only available if the humidifying unit is enabled in the
A/C gateway configuration (see section 2.4.1) and a Mode allowing
humidity control has been selected in the parameter above (Heating,
Cooling or Dry mode). Otherwise this parameter will be disabled indicating
“Not Available” or “Not Available (mode)”, respectively.
If Dry mode is established in the initial configuration,
“Last (Before
Restart)
” and “Off” options will not be available. This fact is due to Dry
mode involves a humidity control, so it is not possible to establish off
humidity control.
Setpoint
:
“Last” or any value between 10ºC and 32ºC.
On the other hand, the status objects can be sent to the KNX bus when applying the
initial settings:
Send initial configuration
:
If enabled, the status objects will be sent to the
KNX bus after applying the initial configuration.
Note
:
even if this option is not enabled, the status objects may be sent to the
KNX bus if the initial configuration differs from the current status of the A/C
machine
.
2.4.3
SCENES
The Scenes function allows defining a set of statuses (in terms of On/Off, mode, fan
speed, etc.) that KLIC-DD3 will send to the A/C unit whenever it receives the
corresponding scene values from the KNX bus.