KLIC-DI SKY
http://www.zennio.com
Technical Support:
http://support.zennio.com
24
3.3
MODE
As explained in section 3.1, the Mode specific window allows configuring what type of
communication objects will be required for controlling the mode of operation of the A/C
machine.
Figure 16.
Mode window
Individual modes
: selecting this option brings 10 new 1-bit communication
objects, five of which will be associated to the reception, from the KNX bus, of
mode switch orders (Auto, Cool, Heat, Fan and Dry, respectively) while the
other five will be used by KLIC-DI to inform the KNX bus about the updated
state of each function, as it is sent by the A/C machine.
Equivalently, the 1-byte objects "
Mode
" and "
Mode (status)
" are available by
default and permit switching between the different modes of operation as well
as checking the currently active mode, respectively.
In case of having activated the
Individual modes
option, it will be possible to
switch from one mode to another by simpl
y sending the value “1” to the
control object corresponding to the new mode. After that, KLIC-DI will
acknowledge the new mode by sending a “1” through the status object
(unless the machine has, for whatever reason, not changed the mode).
Simplified mode
: enabling this option activates the "
Simplified Mode
" 1-bit
object. This object allows switching from the Cool and the Heat modes by
respectively sending the values “0” or “1” to the object. Associated to this
control object, a status object is also enabled
. It will acquire the value “0” for
modes
Cold
and
Dry
, and the value “1” for mode
Heat
. Switching to the
Fan
mode does not change the value of this object.