Note
:
on certain A/C unit models, positions 3-5 may not be available under the Cool
mode, as a measure to prevent that a cold air flow is outputted directly to particular
points of the room where people are supposed to stand. Analogously, positions 1 and 2
may not be permitted by the A/C unit under the Heat mode, to prevent hot air
accumulation on the top of the room.
3.2.8
INDOOR TEMPERATURE SENDING TIME
The “
Indoor Temp. Sending Time
” parameter permits defining a period, between 30
and 255 seconds, to cyclically send the internal temperature measured by the A/C
machine itself and sent to KLIC-DI during the internal communication process. This
value will be sent to the KNX bus through the “
Internal Temperature (status)
” object.
Note that it will be sent even if the value is equal to the last one sent, and that in the
event of non having a built-in sensor in the machine for performing this measure,
abnormal values may be sent to the bus.
3.3
MODE
As explained in section 3.1, the Mode specific window allows configuring the type of
the communication objects that will be required for controlling the mode of operation of
the A/C machine.
Figure 15.
Mode window
Auto Mode
: defines whether the “Auto” mode is available in the A/C unit or
not. If set to “Yes”, KLIC-DI will switch the unit to that mode on the arrival of
the value “0” through the “
Mode
” object (and of the value “1” through “
Auto
Mode
”, in case of having activated the “
Individual Modes
” parameter,
explained below). Afterwards, KLIC-DI will confirm that the unit has switched
to the “Auto” mode by sending the “
Mode (Status)
” object as well as, if
enabled, the “
Auto Mode (Status)
” object.